3.1 Installation Notice

1) The installation of Castle EX series products must be performed in compliance
with the electrical code by professional personnel.
2) Install the UPS in a clean and stable environment that is free of vibration, dust,
high humidity, flammable gas, and flammable liquid or caustic substance.
3) To ensure normal UPS performance, ambient temperature should range
between 0-40℃. If temperature exceeds 40℃, maximum load should be
decreased progressively by 12% of the rated amount along with every increase
of temperature by 5℃. The maximum am- bient temperature for normal UPS
performance should not exceed 50℃.
4) It is suggested that battery pack should work within a temperature range
from15℃ to 25℃.
5) Altitude for normal UPS function should not exceed 1000m. Should UPS be
intended for application above 1000m, contact your service representative for
important information about high altitude operation.

3.2 Required Clearance for Installation

The UPS cabinet uses forced air cooling to regulate internal component
temperature. Air inlets are in the front of the cabinet and outlets are in the back
of the cabinet. Allow clearance in front of and in back of the cabinet for proper air
circulation.
From Top of Cabinet
From Front of Cabinet
From Back of Cabinet
From Right Side of Cabinet
From Left Side of Cabinet
* some components need top access for 60KS/80KS service operation, please
reserve at least 600mm space in the top of unit.
* If customer need smaller clearance requirement of rear side(<600mm), should
check with service if it is allowed to move away the UPS when do maintainence.
≧300 mm (12") working space*
≧900 mm (36") working space
≧600 mm (23.6") working space*
≧50 mm (23.6") working space*
≧50 mm (23.6") working space*