2. Installation

2.1 Unpacking and inspection

1) Unpack the packaging and check the package contents. The ship-
ping package contains:
A UPS
A user manual
A communication cable
A battery cable (for C6KS(e)/C10KS(e) )
2) Inspect the appearance of the UPS to see if there is any damage
during transportation. Do not turn on the unit and notify the carrier
and dealer immediately if there is any damage or lacking of some
parts.
2.2 Input and output power wiring and protective earth
ground installation
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far
away from water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked.
Allow at least 0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked in a
very low temperature environment. In this case it is necessary to
wait until the UPS is fully dried inside out before proceeding instal-
lation and use. Otherwise there are hazards of electric shock.
2. Installation
Installation and wiring must be performed in accordance with the local
electric code and the following instructions by professional personnel.
For safety, please cut off the mains power breaker before installation.
The battery breaker also needs to be cut off if it is a long backup time
model ( " S" model).
1) Open the terminal block cover located on the rear panel of the UPS,
please refer to the appearance diagram.
2) For C6K(e)/C6KS(e) UPS, it is recommended to select the UL1015
10AWG(6mm
AWG Standard for the UPS input and output wirings.
4
2
) wire or other insulated wire which complies with