6.4.4.

Terminal compartment: close

SAREx 16.2 Control unit - electromechanical
For loop topology, automatic termination is performed once the actuator controls
are connected to the power supply.
In case of a power outage of actuator controls, the two RS-485 loop segments
will be automatically connected so that the actuators following these segments
remain available.
When using a SIMA master station, a redundant loop topology may be estab-
lished.
Connect fieldbus cables:
1.
Connect bus cables.
2.
If the actuator is the final device in the fieldbus segment (line topology only):
2.1 Connect termination resistor for channel 1 through linking the terminals
31 - 33 and 32 - 34 (standard)
2.2 For AUMA redundancy I or II: Connect termination resistor for channel 2
through linking the terminals 35 - 37 and 36 - 38.
Figure 43: Close terminal compartment
[1]
Cover (figure shows KP version)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland
[6]
Flameproof frame
1.
Clean sealing faces of cover [1] and frame [6].
2.
Check whether O-ring [3] is in good condition, replace if damaged.
3.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4.
Fit cover [1] and fasten screws [2] evenly crosswise.
5.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
Electrical connection
41