266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A
... 7 Commissioning

Configuration via the LCD indicator with the operating buttons (optional)

Note
For a detailed description of the individual parameters and
menus on the configuration level, please refer to Overview of
parameters on the configuration level on page 49.
The LCD display is only used for visualization of the measured
values and for configuration of the display and of the
transmitter.
In addition, diagnostics messages are displayed.
Parameterization via the 'Easy Setup' menu function
The device can be factory parameterized to customer
specifications upon request. If no customer information is
available, the device is delivered with factory settings.
The setting of the most current parameters is summarized in the
'Easy Setup' menu.
Process display
1. Press the operating key
symbols are shown left and right in the lower process
display.
2. Change to the configuration level with
Easy Setup
Exit
Select
3. Use
or
to select 'Easy Setup'.
4. Confirm the selection with
Easy Setup
Language
Deutsch
Next
5. Use
to call up edit mode.
6. Use
or
to select the desired language.
7. Confirm the selection with
8. Go to the next menu item with
and keep it depressed until both
.
.
Edit
.
.
Easy Setup
Tag
ABB266
Next
9. Use
to call up edit mode.
10. Enter the desired measurement point code
11. Confirm the selection with
12. Go to the next menu item with
Easy Setup
PV Unit
kPa
Next
13. Use
to call up edit mode.
14. Use
or
to select the desired unit.
15. Confirm the selection with
16. Go to the next menu item with
Easy Setup
PV Lower Range Value
0.0000 kPa
Next
17. Use
to call up edit mode.
18. Use
or
to set the start of the measurement range
(LRV).
19. Confirm the selection with
20. Go to the next menu item with
Easy Setup
PV Upper Range Value
0.0000 kPa
Next
21. Use
to call up edit mode.
22. Use
or
to set the end of the measuring range (URV).
23. Confirm the selection with
24. Go to the next menu item with
Edit
.
.
Edit
.
.
Edit
.
.
Edit
.
.