2-sensor input functionality / Dual sensor mode
Fig. 28: Alarm pulse signaling in redundancy mode for failure of the temperature characteristic for sensor 2
1 Temperature characteristic
for sensor 1 ------
2 Temperature characteristic
for sensor 2
3 4 ... 20 mA output signal
Example:
If a pulse rate of 10 seconds is set, the normal temperature signal of 4 ... 20 mA is found at the
output due to the pulse width refresh rate of 60 seconds after a 10-second pulse diagnostic
alarm signal, e.g., of 22 mA for 50 seconds.
The next cycle begins with a 10-second diagnostic alarm signal and subsequently again after 50
seconds with the normal 4 ... 20 mA temperature signal
46
4
5
4 Alarm pulse:
5 Wire break temperature characteristic 2
TTF350
Off
On -> Configurable pulse width
Continuous pulse
OI/TTF350-EN