ABB TTF350 Operating Instructions Manual page 29

Field mounted temperature transmitters
Hide thumbs Also See for TTF350:
Table of Contents

Advertisement

5.5.2.5
Dust-explosion protection Zone 20:
Transmitter design: ATEX II 1D IP65 T135°C
Fig. 17
A Sensor
B TTF350 transmitter
C Power supply
The electric circuit of the transmitter must be limited by an upstream fuse per IEC 127 with a
fuse current rating of 32 mA. This is not required if the power supply is in intrinsically safe "ia"
design.
OI/TTF350-EN
Explosion-protection zone 20
J
A
E
B
D Fuse, 32 mA
E HMI interface for LCD display
TTF350
Electrical connection
Safety area
D
C
A00130
29

Advertisement

Table of Contents
loading