4.3.2 Bracket Installation Procedures:
Step 1: Take the back hanger out from
the package, as shown below.
889mm
Oblong hole 12x18
Step 3: Install handles or lifting rings on both sides of the inverter.
Step 4:
Method 1: Installers hold the handles and hang the inverter on the back hanger.
Method 2: Lift the machine for installation.
09
Step 2: Use the expansion screws in the
accessory pack to fix the back plate on
the wall.
Bracket
Screw
Back hanger
or

4.4 Electrical Installation

4.4.1 AC Terminal Connection
1. Measure the voltage and frequency of the grid-tie connection point to confirm that it meets the
grid-tie specifications of the inverter.
2. It is recommended to add a circuit breaker or fuse on the AC side, whose specification shall be
more than 1.25 times the rated current of the AC output.
3. The PE wire (ground wire) of the inverter must be reliably grounded.
4. Disconnect the circuit breaker or fuse of the inverter and the grid-tie connection point.
5. It is recommended to use copper wire. If you need to use aluminium wire, consult the inverter
manufacturer.
6. Follow the steps below to connect the utility service and the inverter.
Note: Do not connect copper blocks with aluminum wires. Otherwise electrochemical
corrosion will occur and the equipment will be damaged.
• Use copper terminals for copper wires and copper-aluminium terminals for aluminium wires.
Aluminium terminals cannot be used directly.
• Please protect the stripped part with a heat shrink tube after stripping the cable.
Step 1: Select a suitable AC cable and strip the wire.
For specific specifications, refer to the table below.
A1
D+3mm
A2
D+3mm
Heat shrink tube
Code
Description
A1
Wire Length
A2
Wire Length
D
Conductor Length
S
Cross-Sectional Area of Conductor
Cross-Sectional Area of Conductor
S
PE
Step 2: Connect to the communication terminal.
Heat shrink tube
OT terminal
L1/L2/L3/N
PE
S
a
b
c
d
S
D
PE
Specification: M12
Specification: M8
Size: a≤45mm,
Size: c≤30mm,
13.0mm≤b≤15.5mm
8.4mm≤d≤11.0mm
Value
Approximately 500mm
Approximately 380mm
Cold terminal +3mm
70-300mm²
≥S/2
D
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gw73klv-htGw100k-htGw110k-htGw120k-htGw136k-hth