Schematic Diagram Of Main Circuit - Goodwe HT Series User Manual

Solar inverter
Hide thumbs Also See for HT Series:
Table of Contents

Advertisement

Interpretation of overvoltage levels:
If operating voltage of MPPT is greater than 850V, the AC output power decreases when the
voltage increases.
Overvoltage level I: Connect the product to a circuit with measures to limit instantaneous
overvoltage to a relatively low level.
Overvoltage level II: Energy-consuming equipment powered by fixed power distribution devices.
Such equipment includes appliances, portable tools and other household and
similar loads. If there are special requirements for the reliability and applicability
of such equipment, overvoltage level III shall be adopted.
Overvoltage level III: The reliability and applicability of equipment in fixed power distribution
installations must meet special requirements, including switching appliances in
fixed power distribution devices and industrial equipment permanently connect-
ed to fixed power distribution devices.
Overvoltage level IV: The equipment used in the power supply of the power distribution device,
including measuring instruments and prepositioned overcurrent protection equipment, etc.
Interpretation of humid places
Environmental
Parameters
3K3
Temperature range
0°C~+40℃
Humidity range
5% to 85%
Interpretation of environmental levels:
Outdoor inverter: The ambient air temperature range is -25°C~+60℃, suitable for pollution level 3
environment;
Indoor type II inverter: The ambient air temperature range is -25°C~+40℃, suitable for pollution
level 3 environment;
Indoor type I inverter: The ambient air temperature range is 0°C~+40℃, suitable for pollution
level 2 environment;
Interpretation of pollution levels
Pollution level 1: No pollution or only dry non-conductive pollution;
Pollution level 2: Usually there is only non-conductive pollution, but there may be temporary
conductive pollution caused by condensation;
Pollution level 3: There is conductive pollution, or non-conductive pollution becomes conductive
pollution due to condensation;
Pollution level 4: There is persistent conductive pollution, such as pollution caused by conduc-
tive dust or rain and snow.
35
Level
4K2
4K4H
-33°C~+40℃
-20°C~+55℃
15% to 100%
4% to 100%

8.2 Schematic Diagram of Main Circuit

The main circuit of GW100K-HT is shown in the following diagram:
+
MPPT
PV1
Circuit 1
+
MPPT
PV2
Circuit 2
+
MPPT
PV3
Circuit 3
Output
DC Switch
#1
EMI
Filter
+
PV9
MPPT
DC Switch
Circuit 9
#3
+
MPPT
PV10
Circuit 10
DC Switch
DC SPD
#4
Current
Monitoring
The main circuit of GW73KLV-HT/GW110K-HT/GW120K-HT is shown in the following diagram:
MPPT
PV1
+
Circuit 1
MPPT
PV2
+
Circuit 2
MPPT
PV3
+
Circuit 3
DC
DC Switch
EMI
#1
Filter
MPPT
PV10
+
Circuit 10
PV11
MPPT
+
Circuit 11
MPPT
PV12
+
Circuit 12
DC SPD
DC Switch
Current
#4
Current
Monitoring
Monitoring
The main circuit of GW136K-HTH is shown in the following diagram:
MPPT
PV1
+
Circuit 1
MPPT
PV2
+
Circuit 2
PV3
MPPT
+
Circuit 3
DC
DC Switch
EMI
#1
Filter
PV10
MPPT
+
Circuit 10
PV11
MPPT
+
Circuit 11
PV12
MPPT
+
Circuit 12
DC Switch
DC SPD
Current
#4
Current
Monitoring
Monitoring
Output
Inverter
LC Filter
EMI
Circuit
Filter
(DC/AC)
DC Bus
AC Relays
Output
DC/AC
LC
EMI
Inverter
Filter
Filter
AC Relays
Output
DC/AC
LC
EMI
Inverter
Filter
Filter
AC Relays
L1
L2
L3
N
PE
AC SPD
L1
L2
L3
N
PE
AC SPD
L1
L2
L3
PE
AC SPD
36