Electrical Installation - Goodwe HT Series User Manual

Photovoltaic grid-tie inverter
Hide thumbs Also See for HT Series:
Table of Contents

Advertisement

4.3.2 Bracket Installation Procedures:
Step 1: Use the back hanger for
positioning. Drill holes in the wall with a
diameter of 13mm and a depth of 65mm.
The spacing of the holes is shown in the
diagram below.
889mm
Oblong hole 12x18
Step 3: Install handles or lifting rings on both sides of the inverter.
Step 4:
Method 1: Installers hold the handles and hang the inverter on the back hanger.
Method 2: Lift the machine for installation.
09
Step 2: Use the expansion screws in the
accessory pack to fix the back plate on
the wall.
Bracket
Screw
Back hanger
or

4.4 Electrical Installation

4.4.1 AC Terminal Connection
1. Measure the voltage and frequency of the grid-tie connection point to confirm that it meets the
grid-tie specifications of the inverter.
2. It is recommended to add a circuit breaker or fuse on the AC side, whose specification shall be
more than 1.25 times the rated current of the AC output.
3. The PE wire (ground wire) of the inverter must be reliably grounded.
4. Disconnect the circuit breaker or fuse of the inverter and the grid-tie connection point.
5. It is recommended to use copper wire. If you need to use aluminium wire, consult the inverter
manufacturer.
6. Follow the steps below to connect the utility service and the inverter.
Note: Use copper terminals for copper wires and copper-aluminium terminals for aluminium
wires. Aluminium terminals cannot be used directly.
Step 1: Select a suitable AC cable and strip the wire.
For specific specifications, refer to the table below.
L1/L2/L3/N
a
b
D
Specification: M12
Size: a≤45mm, 13.0mm≤b≤15.5mm
Code
Description
A1
Wire Length
A2
Wire Length
D
Conductor Length
S
Cross-Sectional Area of Conductor
Cross-Sectional Area of Conductor
S
PE
A1
D+3mm
S
S
PE
A2
D+3mm
PE
c
d
D
Specification: M8
Size: c≤30mm, 8.4mm≤d≤11.0mm
Value
Approximately 500mm
Approximately 380mm
Cold terminal +3mm
70-300mm²
≥S/2
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gw100k-htGw110k-htGw120k-htGw136k-hthGrid-tie ht seriesGrid-tie gw100k-ht ... Show all