Danfoss VLT FC 103 Operating Manual page 80

Refrigeration drive
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Maintenance, Diagnostics, a...
Symptom
AC drive
deceleration
problems
Table 8.5 Troubleshooting
8
8
78
Possible cause
Motor data are entered
incorrectly.
Danfoss A/S © 04/2018 All rights reserved.
VLT® Refrigeration Drive FC 103
Test
If warnings or alarms occur, see
chapter 8.5 List of Warnings and Alarms.
Check that motor data are entered correctly.
Solution
Increase the ramp-down time in
parameter 3-42 Ramp 1 Ramp-down Time.
Enable overvoltage control in
parameter 2-17 Over-voltage Control.
MG16P222