Danfoss VLT FC 103 Operating Manual page 74

Refrigeration drive
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Maintenance, Diagnostics, a...
Number
3072–5122 Parameter value is outside its limits.
5123
5124
5125
5126
5127
5168
5376–65535 Internal fault. Contact the Danfoss supplier or
8
8
Table 8.4 Internal Fault Codes
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gatedrive card, or the ribbon cable between the
power card and gatedrive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short-circuit connection. Check parameter 5-00 Digital I/O
Mode and parameter 5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove the
short-circuit connection. Also check parameter 5-00 Digital
I/O Mode and parameter 5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For terminal X30/6, check the load connected to terminal
X30/6 or remove the short-circuit connection. Also check
parameter 5-32 Term X30/6 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
For terminal X30/7, check the load connected to terminal
X30/7 or remove the short-circuit connection. Check
parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT
General Purpose I/O MCB 101).
ALARM 43, Ext. supply
®
VLT
Extended Relay Option MCB 113 is mounted without
external 24 V DC. Either connect a 24 V DC external supply
or specify that no external supply is used via
parameter 14-80 Option Supplied by External 24VDC, [0] No.
A change in parameter 14-80 Option Supplied by External
24VDC requires a power cycle.
72
Text
Option in slot A: Hardware incompatible with
control board hardware.
Option in slot B: Hardware incompatible with
control board hardware.
Option in slot C0: Hardware incompatible with
control board hardware.
Option in slot C1: Hardware incompatible with
control board hardware.
Illegal option combination (2 options of the same
kind mounted, or encoder in E0 and resolver in E1
or similar).
Safe stop/safe torque off was detected on a
control card that does not have safe stop/safe
torque off.
Danfoss Service Department.
Danfoss A/S © 04/2018 All rights reserved.
VLT® Refrigeration Drive FC 103
ALARM 45, Earth fault 2
Ground fault.
Troubleshooting
ALARM 46, Power card supply
The supply on the power card is out of range. Another
reason can be a defective heat sink fan.
There are 3 supplies generated by the switch mode supply
(SMPS) on the power card:
When powered with VLT
the 24 V and 5 V supplies are monitored. When powered
with 3-phase mains voltage, all 3 supplies are monitored.
Troubleshooting
WARNING 47, 24 V supply low
The supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply
(SMPS) on the power card:
Troubleshooting
®
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
the allowable limits. The supply is measured on the control
®
card.
Troubleshooting
Check for proper grounding and loose
connections.
Check for proper wire size.
Check the motor cables for short circuits or
leakage currents.
24 V.
5 V.
±18 V.
®
24 V DC Supply MCB 107, only
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC supply is used, verify proper supply
power.
Check for a defective heat sink fan.
24 V.
5 V.
±18 V.
Check for a defective power card.
Check for a defective control card.
If an option card is present, check for
overvoltage.
MG16P222