Electrical Installation
5.8.3 Relay Terminals
RELAY 1
01
02 03
Illustration 5.19 Relay 1 and Relay 2 Terminals
5
5
Relay 1 and relay 2. The location of the outputs
depends on the drive configuration. See
chapter 3.5 Control Shelf.
Terminals on built-in optional equipment. See the
manual provided with the equipment option.
Terminal
01, 02, 03
04, 05, 06
Table 5.4 Relay Terminal Descriptions
5.8.4 Wiring to Control Terminals
The control terminals are located near the LCP. The control
terminal connectors can be unplugged from the drive for
convenience when wiring, as shown in Illustration 5.17.
Either solid or flexible wire can be connected to the
control terminals. Use the following procedures to connect
or disconnect the control wires.
NOTICE
Minimize interference by keeping control wires as short
as possible and separate from high-power cables.
Connecting wire to control terminals
1.
Strip 10 mm (0.4 in) of the outer plastic layer
from the end of the wire.
2.
Insert the control wire into the terminal.
44
RELAY 2
04
05 06
Parameter
Default
setting
Parameter 5-40
[0] No
Form C relay output.
Function Relay
operation
For AC or DC voltage
[0]
and resistive or
inductive loads.
Parameter 5-40
[0] No
Function Relay
operation
[1]
For a solid wire, push the bare wire into
the contact. See Illustration 5.20.
For a flexible wire, open the contact by
inserting a small screwdriver into the
slot between the terminal holes and
Danfoss A/S © 04/2018 All rights reserved.
VLT® Refrigeration Drive FC 103
3.
Description
Illustration 5.20 Connecting Solid Control Wires
Illustration 5.21 Connecting Flexible Control Wires
Disconnecting wires from the control terminals
1.
2.
See chapter 9.5 Cable Specifications for control terminal
wiring sizes and chapter 7 Wiring Configuration Examples for
typical control wiring connections.
push the screwdriver inward. See
Illustration 5.21 Then, insert the stripped
wire into the contact and remove the
screwdriver.
Pull gently on the wire to ensure that the contact
is firmly established and not loose. Loose control
wiring can be the source of equipment faults or
reduced performance.
12 13 18 19 27 29 32 33
12 13 18 19 27 29 32 33
To open the contact, insert a small screwdriver
into the slot between the terminal holes and
push the screwdriver inward.
Pull gently on the wire to free it from the control
terminal contact.
MG16P222