Connection Specifications; Single-Phase Connections (Optional) - ALLIANCE AR105M_X_CONTROL Installation Operation & Maintenance

Cabinet hardmount
Table of Contents

Advertisement

Connection Specifications

IMPORTANT: Connection must be made by a qualified
electrician using wiring diagram provided with ma-
chine, or according to accepted European Union stand-
ards.
Connect machine to an individual branch circuit not shared with
lighting or other equipment. Shield connection in a liquid-tight or
approved flexible conduit. Copper conductors of correct size
must be installed in accordance with National Electric Code
(NEC) or other applicable codes.
Use wire sizes indicated in the Electrical Specifications chart for
runs up to 50 feet [15 m]. Use next larger size for runs of 50 to
100 feet [15 to 30 m]. Use two (2) sizes larger for runs greater
than 100 feet [30 m].

Single-Phase Connections (Optional)

Single Phase Connection - North American Models
Connect the electrical service's wires to the machine's electrical
connection terminal as shown.
Electrical Service Wire
L1
L2
PE
Electrical Connection Terminal Block
Figure 29
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
Machine's Electrical
Connection Terminal
L1
L2
PE (Ground)
Table 16
L2
L3
CHM2496N_SVG
North American Models with Single-Phase Connec-
tion
L2
L1
PE
Single Phase Connection - Models outside of North
America
Connect the electrical service's wires to the machine's electrical
connection terminal as shown.
Electrical Service Wire
U
Neutral
PE
Electrical Connection Terminal Block
51
PE L1L2
CHM2497N_SVG
Figure 30
Machine's Electrical
Connection Terminal
U
N
PE (Ground)
Table 17
N
CHM2499N_SVG
Figure 31
Part No. D1599ENR14