AMU Powercon
Program List and Explanations
5.1.3
5.1.3.1
5.1.4
5.1.4.1
5.2 Signal Outputs
5.2.1
5.2.1.1
5.2.1.2
48
Temp. comp:
Comp.: Available compensation models are:
none
Coefficient
Neutral salts
High purity water
Strong acids
Strong bases
Ammonia, Eth.am.
Morpholine
Quality Assurance: Switch the Quality Assurance on or off.
Level: Select quality level:
Level 0: Off
Quality assurance procedure switched off. Any additional QA
menus are hidden.
Level 1: Trend
Level 2: Standard
Level 3: Crucial
Level 4: User
Edit user specific limits in menu 5.1.4.2
NOTICE: The navigation in the menu <Signal Output 1> and
<Signal Output 2> is equal. For reason of simplicity only the
menu numbers of Signal Output 1 are used in the following.
Signal Output 1: Assign process value, the current loop range and
a function to each signal output.
Parameter: Assign one of the process values to the signal output.
Available values:
Conductivity
Temperature
Sample flow
Cond. uc
Current Loop: Select the current range of the signal output.
Make sure the connected device works with the same current
range.
Available ranges: 0–20 mA or 4–20 mA
A-96.250.331 / 230320