Swann AMU Powercon Operator's Manual page 57

Version 6.20 and higher
Table of Contents

Advertisement

AMU Powercon
Program List and Explanations
5.2.1.43
5.2.1.43.10
5.2.1.43.20
5.2.1.43
5.2.1.43.11
5.2.1.43.21
A-96.250.331 / 230320
Y
a
L
A
Response to maximum control output
B
Tangent on the inflection point
X
Time
The point of intersection of the tangent with the respective axis will
result in the parameters a and L.
Consult the manual of the control unit for connecting and program-
ming details. Choose control upwards or downwards.
Control upwards or downwards
Setpoint: User-defined process value for the selected parameter.
P-Band: Range below (upwards control) or above (downwards con-
trol) the set-point, within the dosing intensity is reduced from 100%
to 0% to reach the setpoint without overshooting.
Control Parameters: if Parameters = Conductivity
Setpoint
Range: 0 S–300 mS
P-Band:
Range: 0 S–300 mS
Control Parameters: if Parameters = Temperature
Setpoint
Range: -25 to +270 °C
P-Band:
Range: 0 to +100 °C
B
A
X
Xp
Tn
Tv
= 1.2/a
= 2L
= L/2
51