Swann AMU Powercon Operator's Manual page 62

Version 6.20 and higher
Table of Contents

Advertisement

AMU Powercon
Program List and Explanations
5.3.2.32.4
5.3.2.32.1
5.3.2.32.21
5.3.2.32.31
5.3.2.32.1
5.3.2.32.22
5.3.2.32.32
5.3.2.32.4
5.3.2.1
5.3.2.24
5.3.2.340
5.3.2.44
5.3.2.54
56
Control Parameters
Range for each Parameter same as
Actuator = Frequency
Examples of metering devices that are pulse frequency driven are
the classic membrane pumps with a potential free triggering input.
Dosing is controlled by the repetition speed of dosing shots.
Pulse frequency: Max. pulses per minute the device is able to re-
spond to. Range: 20–300/min.
Control Parameters
Range for each Parameter same as
Actuator = Motor valve
Dosing is controlled by the position of a motor driven mixing valve.
Run time: Time needed to open a completely closed valve.
Range: 5–300 Sec.
Neutral zone: Minimal response time in % of the runtime. If the re-
quested dosing output is smaller than the response time, no
change will take place.
Range: 1–20 %
Control Parameters
Range for each Parameter same as
Function = Timer:
The relay will be activated repetitively depending on the pro-
grammed time scheme.
Mode: Operating mode (interval, daily, weekly)
Interval/Start time/Calendar: Dependent on options operating
mode.
Run time: time the relay stays active.
Range: 5–32'400 Sec
Delay: during run time plus the delay time the signal and control
outputs are held in the operating mode programmed below.
Range: 0–6'000 Sec
5.2.1.43, p.
51.
5.2.1.43, p.
51.
5.2.1.43, p.
51.
A-96.250.331 / 230320