Communications wiring

LonWorks

When you handle the LonWorks Option Card:
Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
Do not touch components or leads.
Handle the board by its edges.
Isolate from high voltage or electrostatic discharge.
Ensure that you are properly grounded.
Refer to Appendix E (page 51) for the LonWorks Protocol Implementation Conformance Statement (PICS).

To set up the RTU Open for the LonWorks Option Card (Part #LON-OC)

1
Turn off the RTU Open's power.
NOTES
Changes made to the switches when the controller is on will not take effect until the power has been
cycled!
The controller's rotary address switches are not used when the LON-OC is installed. That's because each
LON-OC has a 48-bit Neuron ID that makes it unique on the LonWorks network.
2
Set the Comm Selector DIP switches DS1 and DS2 on SW3 for 38.4k Communications speed. This is the
speed at which the LON-OC speaks to the RTU Open. It is fixed at 38.4k.
3
Set the Comm Selector DIP switches DS3 through DS6 on SW3 for LonWorks. See example below.
4
Set the Comm Selector DIP switch DS7 on SW3 to the ON position to enable the LON-OC.
5
Leave Comm Selector DIP switch DS8 on SW3 in the OFF position since it is not used.
SW3 Protocol Switch Settings for LonWorks
DS8
Off
RTU Open v3
Integration Guide
DS7
DS6
DS5
On
On
Off
Carrier Proprietary and Confidential
14
DS4
DS3
On
Off
CARRIER CORPORATION ©2016