Grounding and Bonding to the SVRS Alarm Power Center
Connect a ground wire from the primary electrical panel to the SVRS Alarm
power center ground bus bar. Also ground each piece of high voltage (120 VAC
or 240 VAC) equipment that is connected to the SVRS Alarm power center
relays. The SVRS Alarm power center must also be connected to the pool
bonding system using an 8 AWG (minimum) wire. An earth terminal for bonding is
provided on the grounding bus bar inside the Power Center. For input AC wiring
information, see page 17.
SVRS Audible Alarm Installation and User's Guide