4
Service / Alarm Mode
Main Menu
[1/5]
Service / Alarm
*Alarm Disabled*
Service Mode
Re-Enable Alarm
System Active
Testing the SVRS Alarm
Main Menu
[2/5]
Tst Alarm Output
Alarm Activating
For 4 Seconds
Alarm Count
Main Menu
[3/5]
Alarm Count
SVRS Audible Alarm Installation and User's Guide
Enter Service mode: Press the Menu button then
the Right arrow button to enter Service mode.
Note: "Service" mode disables the Alarm mode and
allows manual control of the pump. When the SVRS
Alarm is powered up and in "Service" mode, it will
automatically revert to "Alarm" mode (normal SVRS
protection mode) in five (5) minutes and the pump
display will show "DISPLAY NOT ACTIVE."
Exit Service mode: To exit Service mode anytime
before five minutes, press any button on the control
panel. The screen will display "Re-Enable Alarm
System Active" for five (5) minutes then return to
"Alarm" mode. Pressing any button before the five
(5) minutes will return the system to "Alarm" active
mode. Press the Menu button to scroll through the
menu items until the main status screen is displayed.
To test the audible alarm: Press the Menu button
until Main Menu [2/5] is displayed, then press the
Right arrow button. The screen displays "Alarm
Activating for 4 Seconds." The audible alarm is
activated for four (4) seconds. Press the Menu button
until the main status screen is displayed.
To view the Alarm Count screens: Press the
Menu button until Main Menu [3/5] is displayed, then
press the Right arrow button. The screen displays
"Total SVRS Event Count 0." Press the Right arrow
button to view the other Alarm Count events. Press
the Menu button to exit Alarm Count.