Siemens FC361 Series Technical Manual page 79

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

8.5.2.2 Lamp test
A6V10421795_en--_k
The lamp test checks the following functions:
LEDs
Buzzer
LCD
This function is available directly under Main menu for access level 1 if checkbox
'Lamp test activation possible at access level 1' is checked under task card 'Other
settings' in 'FC360 Panel Configurator'.
1. Press
on the keypad. The 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Operation' and press
Operation
1 - Isolation
2 - Test
3. Select 'Test' and press
Test
1 - Detection
2 - Lamp test
3 - Voice test
4. Select 'Lamp test ' and press
Do you want to activate
lamp test?
Yes (OK) or No (C)
5. Press
to confirm. Test starts:
LEDs: on 10 s
Buzzer: on 10 s
LCD: on 5 s, then off
The panel returns to the previous status after finishing check.
Operations under access level 2
L2
. The 'Operation' window is open.
L2
. The 'Test' window is open.
L2
. A confirmation dialog window is open.
Operation
8
79 | 151

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc362 seriesFc361-zzFc361-zaFc362-zzFc362-za

Table of Contents