Siemens FC361 Series Technical Manual page 78

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Operation
8
Operations under access level 2
78 | 151
4. Select 'Detection' and press
Test - Detection
1 - Silent
2 - Audible
5. Select an item, e.g. 'Silent', and press
Detection - Silent
01 Zone 1(OFF)
02 Zone 2(OFF)
T1 Zone T1(OFF)
6. Select the desired zone and press
the zone are displayed.
Detection - Silent
Entire zone (OFF)
001 Manual alarm 1(OFF)
002 Manual alarm 2(OFF)
003 Manual alarm 3(OFF)
7. Select e.g. 'Entire zone' and press
(Warning):All
programmed outputs are
activated.
Do you want to activate
zone test?
Yes (OK) or No (C)
8. Press
. The selected zone is set to 'Test' mode and the 'Test' LED is on.
9. You can start testing devices installed in the zone.
Refer to the steps above to exit the 'Test' mode after testing is finished. Before
exiting the 'Test' mode, ensure no element under a zone/device is activated.
If a zone/device is disabled after it is set to 'Test' mode, the zone/device is still
under 'Test' mode after it is enabled. The LCD still displays test events in fire
alarm situations. Exit 'Test' mode to normalize the zone/device function in fire
alarm situations.
. The 'Detection' window is open.
L2
. A list of all zones is displayed.
L2
. 'Entire zone' and a list of all devices under
L2
. A confirmation dialog window is open.
A6V10421795_en--_k