Siemens FC361 Series Technical Manual page 80

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Operation
8
Operations under access level 2
8.5.2.3 Voice test
80 | 151
This function checks if voice alarm devices play the voice test message (M4) in a
specific language order defined under task card 'Site' in 'FC360 Panel
Configurator'.
You can activate/deactivate voice test locally in the fire control panel via menu
operation, or remotely in the configuration tool via input modules, I/O modules or
digital inputs on the mainboard IO (see document
If you want to deactivate voice test after you've activated it, the audio doesn't stop
at once unless the voice test sequence is completed. However, if a real fire event
occurs during a voice test, the message with a higher priority is played
automatically.
To activate/deactivate voice test in the fire control panel
1. Press
on the keypad. The 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Operation' and press
Operation
1 - Isolation
2 - Test
3. Select 'Test' and press
Test
1 - Detection
2 - Lamp test
3 - Voice test
4. Select 'Voice test' and press
Test - Voice test
1 - Voice test (ON)
2 - Voice test (OFF)
5. Select '1 - Voice test (ON) ' and press
Voice test (OFF)' and press
A6V10450595
L2
. The 'Operation' window is open.
L2
. The 'Test' window is open.
L2
. The 'Voice test' window is open.
L2
to activate voice test, or select '2 -
to deactivate voice test.
for more details).
A6V10421795_en--_k