RS485 module
A6V10421795_en--_k
DTE-HOST
DCD
DSR
CTS
0 V
RXD
DTR
TXD
RTS
T Participant with RS232 interface
RS485
PIN
Designation
4
RS485_A
3
RS485_B
2
-
1
-
Admissible cable cross-section: 0.2...1.5 mm²
X2
RS485_A
A
RS485_B
B
T1
First participant
Tn
Last participant
*) Stub lines must not exceed 20 m!
Do not forget about the polarity A, B!
Up to eight participants are allowed.
Terminate the line after the last participant with 120 Ω!
Use shielded cables.
Configuration:
The participant address and communication trouble setting can be configured in
'FC360 Panel Configurator'. See document
parameter settings are not configurable.