6.2 Surface mounting

A6V10421795_en--_k
Steps:
1. Define the mounting location.
2. Open the door of the panel using a screw driver.
3. Break out the required cable entries (A).
Screw cable glands (B) for all open entries. The cable glands are not
included.
The mains cable must be fed into housing on the right from above. Signal
and control cables can be fed into housing through the remaining entries.
4. Mark position of mounting holes (D) on the wall.
5. Drill the holes and insert rawl plugs (not included).
6. Attach and fasten the panel using screws (Ø ≥5 mm, not included).
7. Stick the supplied aluminum stickers over all holes for wall mounting.
8. Optional: Mounting accessories (C). See 'Accessories [➙ 46]'.
9. Switch off the mains supply AC 230 V and connect the mains cable. See
'Power supply - mains voltage [➙ 30]'.
10. Connect signal and control cable (↑ detector lines, sounder lines,
inputs/outputs and relays). See 'C-NET detector line [➙ 33]', 'Sounder lines
[➙ 40]', 'Inputs/outputs [➙ 41]', 'Relay [➙ 43]'.
11. Switch on mains supply AC 230 V.
12. Connect batteries. See 'Battery [➙ 31]'.
 The panel is ready for commissioning. See 'Commissioning [➙ 109]'.
13. Test the functionality of the panel.
14. Close the door of the panel.
 Hand over the system to the customer.
Fig. 4: Details of mounting
A Cable entries
B Cable glands
Installation
Surface mounting
C
Accessories
D
Mounting holes