6.11.2 Evacuation module (FTO3601-H1) [NL]

A6V10421795_en--_k
Fig. 16: Installation of evacuation module (NL)
Function:
The evacuation module (NL) provides the Dutch special function. It activates all
sounder lines and alarm devices of 'EVAC siren' and 'EVAC voice' types by
pressing the <START> button twice and deactivates these devices by pressing the
<STOP> button twice. Once activated, alarm devices on sounder lines play the
'Continuous' tone, EVAC voice devices make the sound following the pre-set audio
sequence ('Continuous' tone --> voice message), and EVAC siren devices play the
tone configured in 'Addressable sounders tone 1' under task card 'Site' in FC360
Panel Configurator.
Installation:
Detailed information on installation is available in document A6V10431009. See
chapter 'Applicable documents [➙ 9]'.
Configuration:
The evacuation module (NL) is configured by default when starting up with country
setting 'NL: With FTO3601 H1 (EVAC field)'.
Operation:
1
2x Start
2x Stop
2
Storing
Ontruimingsalarm
Fig. 17: PMI of evacuation module (NL)
No. Description
1
LED: EVAC
devices active
2
LED: EVAC fault Flashing
3
Button: 'START' -
4
Button: 'STOP'
FTO3601-H1
3
4
Status
Function
On
Devices of 'EVAC siren' and 'EVAC voice'
types are activated.
One or more alarm devices are in fault.
On
All alarm devices are disabled.
Press twice quickly to start all alarm devices.
-
Press twice quickly to stop all alarm devices.
Installation
6
Accessories
47 | 151