6.8 Inputs/outputs

A6V10421795_en--_k
The panel mainboard has four configurable inputs/outputs. Each one can be
configured as an input or output.
The default settings are:
IO1/IO2: input
IO3/IO4: output
Fig. 12: Connection of configurable IOs
1 Configured as input (Connect to '0V' and IO)
2 Configured as output (Connect to '24V' and IO)
Configured as 'input'
The inputs can be triggered by a potential-free contact. They can be configured as
one of the following usages:
Class Change Usage
Evacuation usage
Reset command
Access level 2
Disable RT Fire and RT Fault devices
Activate manned
Toggle between manned/ unmanned
Initiate extra PSU fault
Dialer (RT Fire Device) Fault
Initiate fire brigade is called
Acknowledge command
Voice test Usage
Door holder off
A6V10450595
See document
Configured as 'output'
Configuration as 'output' allows the activation of external devices (e.g. relays) with
24 V voltage.
The line is not monitored.
for detailed description of each usage.
Installation
6
Inputs/outputs
41 | 151