Specifications
1.2 Specifications
MS-9200UDLS PN 52750:A 11/04/05
•
Telephone Line Active LEDs
•
Communication Confirmation (Kissoff) LED
•
Touchtone/Rotary dialing
•
Programmable Make/Break Ratio
•
EIA-232 Printer/PC interface (variable baud rate)
•
80-character LCD display (backlit)
•
Real-time clock/calendar with daylight savings time control
•
History file with 1,000 event capacity
•
Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
•
Waterflow selection per module point
•
Alarm verification selection per detector point
•
Walktest, silent or audible
•
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
•
Silence inhibit timer option per NAC
•
Autosilence timer option per NAC
•
Continuous, March Time, Temporal or California code for main circuit board
NACs with two-stage capability
•
Selectable strobe synchronization per NAC
•
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules,
AFM annunciators or LCD-80F Remote annunciator
•
Auto-program (learn mode) reduces installation time. Reports two devices set to
the same address
•
Password and key-protected nonvolatile memory
•
User programmable password
•
Fully programmable from local keypad or optional keyboard
•
Upload/Download (local or remote) of program and data via integral DACT
•
Compatible with Fire-Lite's newer series devices (refer to SLC Wiring Manual
for a list of compatible addressable devices)
•
Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to
the SLC Wiring Manual for a list of compatible addressable devices)
•
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
•
Annunciators:
ACS Series-LED Zone Annunciators
LDM Graphic Annunciator Series
LCD-80F Liquid Crystal Display point annunciator
ACM-8RF Relay Module
Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB11
MS-9200UDLS: 120 VAC, 60 Hz, 3.0 amps
MS-9200UDLSE: 240 VAC, 50 Hz, 1.5 amps
Wire size: minimum 14 AWG (2.00 mm
Product Description
2
) with 600 V insulation
13