R E D U ND A N C Y
6.2.2. M10x-M Redundant Configuration
The redundant configuration requires M10x redundant communication setting to be enabled
either through MD panel on MNS module front or through MNavigate as shown in Table 7.
Table 7 M10x-M redundant communication setting
6.2.3. MNS Digital Gateway Redundant Configuration
Configuration and Parameterization of MNS Digital [Upgrade] projects are done via MNavi-
gate tool.
The parameters must then be downloaded to both the Primary and Backup MNS Digital
Gateway to become effective.
In a project with multiple MNS Digital Gateway the majority of the MNS Digital Gateway pa-
rameter are identical. To ease the parameterization such parameters could be copied among
the MNS Digital Gateway (Assign to MNS Digital Gateway).
As Network address settings are different between the MNS Digital Gateway s if connected
to the same network those have to be configured individually
The steps of configuring the redundant MNS Digital Gateway is as following:
1. Set the Ethernet IP address of LAN1 and LAN2 for Primary and Backup MNS Digital
Gateway.
Figure 23 MNavigate IP address Parameterization for Primary and Backup MNS Digital Gate-
way
1TG C 9 0 8 0 0 4 M 0 2 0 1
MNavigate tool
R ED U ND A N C Y CO N F IG U R AT IO N
MCUSetup tool
2 7