Wiring the UC Open for power

WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
The UC Open is powered by a Class 2 power source. Take appropriate isolation measures when mounting it in
a control panel where non-Class 2 circuits are present.
Carrier controllers can share a power supply as long as you:
Maintain the same polarity.
Use the power supply only for Carrier controllers.

To wire for power

1
Remove power from the power supply.
2
Pull the screw terminal connector from the controller's power terminals labeled Gnd and Hot.
3
Connect the transformer wires to the screw terminal connector.
NOTE If using a grounded transformer, connect the ungrounded lead to the Hot terminal to avoid damaging
the transformer.
4
Apply power to the power supply.
5
Measure the voltage at the UC Open's power input terminals to verify that the voltage is within the operating
range of 21.6–26.4 Vac.
6
Insert the screw terminal connector into the UC Open's power terminals.
7
Verify that the Power LED is on and the Run LED is blinking.

Addressing the UC Open

You must give the UC Open an address that is unique on the network. You can address the UC Open before or
after you wire it for power.
1
If the UC Open has been wired for power, pull the screw terminal connector from the controller power
terminals labeled Gnd and Hot. The controller reads the address each time you apply power to it.
UC Open
Installation and Start-up Guide
5
Installing the UC Open
CARRIER CORPORATION ©2019
All rights reserved