Mounting

Mounting

1.7 Introduction

This chapter deals with the following mounting alternatives:
 Surface mounting
 Flush mounting in a wall
For surface mounting and flush mounting in a wall, a stand-alone
cabinet is used.

1.8 Location

The Fire Alarm aControl Panel must be located in, or near by, the
entrance. Both the Fire Alarm Control Panel and the Controller must
be placed according to local regulations and in consultation with the
fire brigade.

1.9 Mounting Height / Space Requirement

To ensure optimal readability of the Fire Alarm Control Panel's
display, the recommended mounting height of this cabinet top is
approximately 175 cm above the floor.
For surface mounting and flush mounting in a wall, there must be a
free space of minimum 50 mm from the cabinet top to the ceiling in
order to fasten the top screw on the front panel door after the
installation. A crosshead screwdriver can be used for this purpose.
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE,
Rev. J, 2011-12-06,
Autronica Fire and Security AS