Page 1
AutroSafe Interactive Fire-Alarm System Interfacing Analogue Addressable Loops Loop Protocols BS-3, BS-30, BS-60, BS-80, BS-90 and BS-100 Protecting life, environment and property... P-ASAF-BS100/EE Rev. B, 2006-10-26...
Page 2
This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidiaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it.
BS-100 Loop Data Shown in the AutroSafe Configuration Tool ..15 5.3.1 Detection Zone Text..............15 5.3.2 Loop-Unit Tag Names – Detector Addresses......15 Loop Topology for BS-100 Interfaced Detectors....... 16 Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 1...
Page 4
5.12 Configuring Control Outputs.............. 23 6. Commissioning ..............24 Commissioning Procedure ..............24 Short-Circuit Test ................24 Verifying the Loop Interface .............. 25 7. Reader’s Comments ............27 Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 2...
This includes detectors used in systems BS-3, BS-30, BS-60, BS-80, BS-90 and BS-100. 1.2 The Reader The handbook is intended for use by trained and qualified Autronica Fire and Security service/technical personnel responsible for the installation, configuration and commissioning of the AutroSafe Interactive Fire-Alarm System.
(maximum 99 addresses), can be connected to each Loop Interface. 2.2 Dimensions 95x 89x32 mm (depth x height x width) Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 4...
Al arm LED 8 LED 1 *ASSP: Autronica Standard Short Protocol (communication protocol for BS-100 loop communication) ** Al_Com+ com: AutroSafe Loop Communication (communication protocol for the AutroSafe loop communication) Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26,...
BSS-310 and BSS-310A. 200,5mA from regulated 5VDC is too much for BSS-310. Conclusion: the configuration is OK if the power module BSS-310A is used. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 7...
• printout of detector sensitivity beyond limit • printout of customer-specified configuration from front panel • BK-50 functions (zone-control unit in the BS-60 system) Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 8...
(response time). In order to meet this requirement, manual call- points cannot be assigned an address higher than 40 on an analogue addressable loop. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 9...
337 and an RS-232/20mA CL Converter BSL-12/2. There can be a maximum of 32 panels divided on 2x16 panels, connected to 2 serial communication ports on EAU-321. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 10...
8 BSD-330s at different delay periods. The random delay period is printed on the acceptance label on the Loop Interface (BSD-330). Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 11...
• If a BSDETECT.DAT. file is not available, the loop units and corresponding data have to be added manually using the AutroSafe Configuration Tool. See chapter 5.7. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 13...
Detector Address on the loop (01-99) Loop Address (00-15) Panel Address (If more than one panel is used, prefixes A to Z are used) Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 14...
(for example, BS100_LOOP_UNIT, 0001). If more than one panel is used, prefixes A to Z must be added manually. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 15...
BS-100 loop units in the “Tree View” does not show the loop topology. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 16...
BS-100, BS-80 or BS-90. This menu selection is found in the “Tools” menu. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 17...
• In the “Tree View”, select the BS-320 panel • Click the “Browse” button, locate the BSDETECT.DAT. file in the FireSys site folder, and click “Open” Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 18...
Page 21
(“Add BS100 loop to panel”). The Loop Interfaces and all loop units will be imported into the AutroSafe Configuration Tool Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 19...
Page 22
Configuration Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 20...
Page 23
Note that the length of the detection zone text will not be changed (a maximum of 34 characters). Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 21...
Filter Constant Filter function for the entire loop. Response period: Normal or Long Name The name of the unit, maximum 24 characters Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 22...
The functionality of the control output, and particularly the reset function, is similar to standard control outputs. Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 23...
To overcome this problem, a random delay period has been configured for each Loop Interface. A random delay period is printed on the acceptance label on the Loop Interface (BSD- 330). Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS Page 24...
LED 6 (yellow): Steady light upon detector failure LED 7 (yellow): Steady light at prealarm LED 8 (red): Steady light at alarm *ASSP: Autronica Standard Short Protocol (communication protocol for BS-100 loop communication) ** Al_Com+ com: AutroSafe Loop Communication (communication protocol for the AutroSafe loop communication) Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26,...
Title: Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System Reference number: P-ASAF-BS100/EE Rev.B, 2006-10-26 Your information on any inaccuracies or omissions (with page reference): Please turn the page Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS...
Page 30
------------------------------------------------------------------------------------------------ Fax: ------------------------------------------------------------------------------------------------ Date: ------------------------------------------------------------------------------------------------ Please send this form to: Autronica Fire and Security AS N-7483 Trondheim Norway Tel: + 47 73 58 25 00 Fax: + 47 73 58 25 01 www.autronicafire.com Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26,...
Page 31
Reader’s Comments Interfacing Analogue Addressable Loops, AutroSafe Interactive Fire-Alarm System P-ASAF-BS100/EE Rev.B, 2006-10-26, Autronica Fire and Security AS...
Page 32
Autronica Fire and Security AS is an international company, based in Trondheim, Norway, and has a world-wide sales and service network. For more than 40 years Autronica’s monitoring systems have been saving lives and preventing catastrophes on land and at sea. Autronica Fire and Security’s most important business area is fire detection and security.