Page 1
Release 4 Operator's Handbook AutroSafe Interactive Fire Detection System 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire And Security AS...
Page 2
This product should not be mixed with other commercial wastes for disposal. Operator's Handbook, AutroSafe Interactive Fire Detection System, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security...
Page 4
10.2 Show Status Menu ................65 10.3 Show Status - Fire Alarms..............66 10.4 Show Status – Fire Warnings ............67 Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 4...
Page 5
13.7 How to Change Language..............95 13.8 How to Initialize the Fire Alarm System ..........96 13.9 Cancel Inhibited Points ..............97 Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 5...
Page 6
15.2.4 Operation Zone ............... 153 15.2.5 Configuration Example ............154 15.3 Action Digits Table - Operation Mode ..........155 15.4 Menu Structure .................. 157 Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 6...
The AutroSafe Interactive Fire Alarm System comprises various components. It is important that the reader gets familiarized with these, plus the different terms and abbreviations.. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 7...
Item G and H and some other items may need to be provided with a seperate power supply. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 8...
2.1 Introduction 2.1.1 Panel Variants The user interface and operation of the Fire Alarm Control Panel BS-420 and the Operator Panel BS-430 are identical. The panel is therefore referred to as the operator panel throughout this handbook (refer to chapter 2.2).
The operator panel consists of two main sections. The upper section, and the lower section which is the Operator Part. The standard onshore market version BS-420 is shown below. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,...
The panel displays information on fire alarms occurring in all operation zones. However, the level of details of the given information depends on which operation zone the information is related to. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 12...
No further details are available. Each of the conditions are presented in a separate condition window, in one mode only. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 13...
6 faults and disablements (using the More Events Button). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 14...
Panel Overview 2.5 The Menu Display 2.5.1 Operator Panel This chapter applies to the BS-420 / BS-430 panels, as well as the BU-BV-420 panels. During Normal Operation, the backlight in the menu display is always on. The menu display has 16 lines of 40 characters.The display is divided into several display windows showing different types of information.
To decrease the contrast, press and hold down the More Events button, while pressing the green Reset System button. More Events Button Front Push Buttons Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 16...
Steady yellow light when a system fault within the operating zone of the operator panel is present. Power Steady green light when power is ON. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 17...
Panel Overview 2.7.2 The Operator Section (lower left section) Applies to the operator panels BS-420 / BS-430. Function Delayed Steady yellow light indicates that Immediate Output Actioning has been disabled (manual operation in Menu Mode), i.e. a delay period is active for Fire Alarm Devices (FAD) or Fire Alarm Routing Equipment (FARE).
Panel Overview 2.7.3 The Operator Section (lower right section) Applies to operator panels BS-420 / BS-430. Dual Safety Stdby Applicable to systems using the Dual Safety concept; a system with redundant loop control consisting of a Primary and Secondary System.
More Events Button (Front Push Button) Front Push Buttons Utility Buttons (BS-420 / BS-430) Alphanumeric Keyboard (BS-420 / BS-430) Manoeuvre Buttons (BS-420 / BS-430) Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 20...
Page 21
(black) active window (scroll page by page). Possible only if there are more alarms than possible to display in the window. 2.8.1.2 Utility Buttons Applies to the BS-420 / BS-430. Utility Buttons Button Designation Menu (black) Used to toggle between Operation Mode and Menu Mode.
Page 22
2.8.1.3 Alphanumeric Keyboard The alphanumeric keyboard (Fire Alarm Control Panel/Operator Panel) includes the numbers 1 to 9, the letters a to z and other feature keys (see table below). Applies to the BS-420 / BS-430. Alphanumeric Keyboard Button Designation Star key (asterisk key) Not yet supported.
Page 23
Panel Overview 2.8.1.4 Manoeuvre Buttons Applies to the BS-420 / BS-430. Manoeuvre Buttons Button When accessible (mode) Description Enter When the cursor is on a list The properties of a selected unit is item. shown. The selected menu page on the display is shown if the item is a submenu.
Used to scroll pages of information related to the (black) selected condition window, if there are more events than the display can show. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 24...
The buzzer can be silenced by pressing the Mute Panel button. If the reason for the buzzer signal still exists, the buzzer will resound after a predefined time. 2.9.1 Operator Panel BS-420/BS-430 The internal buzzer on the BS-420/BS-430 is activated in the cases of: System Fault Faults ...
(start up) - idle state when pressing the menu button in Menu Mode, which will leave menu mode from all menu levels Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 26...
Mechanical tool. Accessible by persons doing repair work and changing firmware. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 27...
The optional alarm presentation with zonal indication is used throughout the handbook. The different events, for example, «In the Event of a Fire Alarm», are presented in Operation Mode. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 28...
Latest zone in alarm Latest zone in alarm Zones: 2 Zones: 2 Main building Show room gr. floor Main building Show room gr. floor Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 29...
Total number of zones in alarm Zones in alarm 19:23 FIRE ALARMS Total: 3 1 OFFICES 2 CANTEEN 3 WORKSHOP Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 30...
Close Window button to re-enter Operation Mode in order to activate the Silence Alarms button and the Reset button. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 31...
Close Window button to re-enter Operation Mode in order to activate the Silence Alarms button and the Reset button. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 32...
In Appendix you will find a table providing a complete list of all Action Digits that may appear in Operation Mode. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 33...
Alarm Devices (FAD) have to be silenced / deactivated using the SILENCE ALARMS button. Otherwise the reset operation will be rejected without having any effect on system behaviour (configurable). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 34...
equivalent with Zone, except from that the command is issued to AutroSafe over the AutroCom connection. Applicable to Points only. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 35...
In other words, all loop units (except Points which have this memory function, see above) will be enabled when enabling the corresponding loop. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 36...
Alarm (must be confirmed by the operator). Alarm disabling may later be cancelled and the points made to retransmit their alarm level (Reactivate). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 37...
Immediate Action applies to: Fire Alarm Devices (FAD) Fire Alarm Routing Equipment (FARE) Fire Protection Equipment (FPE) Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 38...
Action digit 2, which represents ACTIVATE. Activation of a manual call point with the Operation Zone will also give immediate action. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 40...
Page 41
1 OFFICES 2 CANTEEN 3 Y WORKSHOP DELAYED OUTPUTS ACTIVATES 19:40 1: SHOW POINTS 2: ACTIVATE 4: PROLONG DELAY Action Digits Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 41...
(configurable) the point(s) in this Delayed Action detection zone has been set to point delay ON (the default configuration) Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 42...
SOLAS applies to fire Alarm Devices (FAD), Fire Alarm Routing Equipment (FARE) - detectors only, and Fire Protection Equipment (FPE) - option. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 43...
The table for the different procedures is divided into four columns with the following headings; Step Actions to be taken Display Indication Audible Indication Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 44...
Page 45
About «In the Event of….» (this page is left blank intentionally) Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 45...
Activated functions: A message is sent to the Fire Brigade. The fire alarm condition activates Fire Alarm Devices (sounders and visual indicators). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 46...
If you want to view detailed information for another zone, select the other zone in step 5, repeat step 6, 7 and 8, then go to step 9. If not, go directly to Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 47...
Page 48
AUTROSAFE SelfVerify SelfVerify If there are points still signalling an alarm when the system is reset, go to the next page. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 48...
Page 49
The red FIRE indicator goes off. The red Fire Brig. Signalled indicator goes off. The panel enters its idle state. AUTROSAFE AUTROSAFE SelfVerify SelfVerify Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 49...
The internal buzzer is activated. Default pattern on the sound: 1 sec. ON, 1 sec. OFF Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 50...
(PROLONG DELAY). The T1 period will terminate, and the T2 period will start. If you do not want to prolong the delay period, go directly to step 9. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 51...
Page 52
If the delay time expires, all fire alarm devices within the alarm zones assigned to the actual detection zones (sounders and visual indicators) will automatically be activated. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 52...
Page 53
The red Fire Brig. Signalled indicator goes off. If there are points still signalling a fire alarm, refer to step 10 in the procedure described in chapter 5.2. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 53...
0,5 sec. ON, 3,5 sec. OFF Activated functions: The Fire Warning state will not activate Fire Alarm Devices (sounders and visual indicators). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 54...
5, repeat step 6, 7 and 8, then go to step 9. If not, go directly to step 9. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 55...
Page 56
RESET 19:23 19:23 button. Info Info : Completed : Completed Comments: The panel enters its idle state. AUTROSAFE AUTROSAFE SelfVerify SelfVerify Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 56...
Fire Alarm Routing Equipment. Activated functions: - The output line from the control and indication equipment is activated. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 57...
CLOSE WINDOW button, then repeat step 5 and 6. If you want to accept each fault warning in turn, go directly to step 7. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 58...
Page 59
AUTROSAFE AUTROSAFE SelfVerify SelfVerify Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 59...
3 CANTEEN 3 CANTEEN Operator Operator Total no. Total no. Last alarm detected Last alarm detected Information Information of alarms of alarms Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 60...
• Available in the Log Menu. read the selected events READ BACKWARDS backwards page by page (if more than one page). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 61...
Press the ENTER button, then use the up/down arrows to move the cursor to the desired selection in the selection field. Refer to the two subsequent chapters. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 62...
ENTER button - (to cancel an input value, press the CANCEL button). 19:23 DISABLE DETECTION ZONES OFFICES Disablement time Hour Min. Execute command Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 63...
DETECTION ZONES OFFICES Disablement time Hour Min. Execute command When all values have been entered, press the ENTER button to accept. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 64...
Standard Control Units Other Outputs Fire Alarm Devices Fire Alarm Routing Equipment Fault Warning Routing Equipment Active Sensors Oil & Gas Inhibited Points Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 65...
To view point(s) in alarm for the selected detection zone, press Action Digit 1 (SHOW POINTS). To return (each step backwards), press the Close Window button Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 66...
To view point(s) in Fire Warning for the selected detection zone, press Action Digit 1 (SHOW POINTS). To return (each step backwards), press the Close Window button Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 67...
Detection Zone in order to accept the fault warning (point). To return (each step backwards), press the Close Window button Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 68...
The 3 steps above will lead you to Show Status - Disablements, where you can continue viewing the status of the disablements (1-8), shown on the following page (step 4). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 69...
Page 70
Action Digit 3 (ENABLE), then If not, go to step 8. To return (each step backwards), press the Close Window button Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 70...
To view point(s) in test for the selected detection zone, press Action Digit 1 (SHOW POINTS). To return (each step backwards), press the Close Window button Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 71...
The 3 steps above will lead you to Show Status – Acitivated Outputs, where you can continue viewing the status of the activated outputs (1-5), shown on the following page (step 4). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 72...
Page 73
AVCITVATED OUTPUTS>DMCU AVCITVATED OUTPUTS>DMCU TOTAL 1 TOTAL 1 press 1*1dc7 1*1dc7 To return (each step backwards), press the Close Window button Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 73...
To select ACTIVE SENSORS, press 7. If there are several active smoke sensors, use the arrow buttons to scroll though the list of points. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 74...
To view inhibited point(s) for the selected detection zone, press Action Digit 1 (SHOW POINTS). To return (each step backwards), press the Close Window button Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 75...
For information on Disablement Sources, refer to chapter 3.16. 11.2 Disable Menu Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 76...
A disablement time can be set. When the disablement time expires, the point(s) will automatically be enabled. The point(s) can also be enabled manually from the Enable Menu. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 77...
Fire Protection Equipment will automatically be enabled. The outputs can also be enabled manually from the Enable Menu. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 78...
The function is useful in situations where you want to disable immediate output actioning at special periods to avoid causing any unnecessary disturbance. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 79...
CANTEEN CANTEEN OFFICES OFFICES WORKSHOP WORKSHOP then move the cursor to the desired selection (OFFICES) by scrolling with the arrow buttons Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 80...
Page 81
Close Window button Comments: If the Close Window button is not pressed, the DISABLE menu will appear automatically after a short moment. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 81...
Enabling 12.2 Enable Menu Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 83...
FAD will be enabled. The FAD will now give an audible indication. You can enable a single unit (FAD) / alarm circuit, or all units (FADs) in a selected Alarm Zone. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 84...
It is possible to enable immediate output actioning for all Day / Night areas or for selected Day / Night areas. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 85...
CANTEEN CANTEEN OFFICES OFFICES then move the cursor to the desired selection WORKSHOP WORKSHOP (OFFICES) by scrolling with the arrow buttons Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 86...
Page 87
Close Window button Comments: If the Close Window button is not pressed, the ENABLE menu will appear automatically after a short moment. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 87...
Only users with access level 2 (key), 3 (password restricted) or a higher access level are allowed to do changes in the system menu. 13.2 System Menu Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 88...
New date (YYYYMMDD) : 19981126 New date (YYYYMMDD) : 19981126 New time (hhmmss) New time (hhmmss) : 142400 : 142400 Successfully Completed Successfully Completed Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 89...
Comments: From here you can enter / leave access level 3, or set a new password (see the next steps on the following pages). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 91...
ACCESS LEVEL 3/LEAVE ACCESS LEVEL 3 Are you sure you want to leave Are you sure you want to leave access level 3? access level 3? Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 92...
Verify by entering the new password, then press SYSTEM 19:23 twice. ACCESS LEVEL 3 / SET PASSWORD New password : Verify password: Successfully Completed Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 93...
To select SYSTEM, press 4. To select PRINTER, press 4. SYSTEM 19:23 PRINTER 1 PAPER FEED To feed paper, press 1. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 94...
7 DAY/NIGHT TIMERS Comments: The System Menu will after a few seconds appear in the native language (shown in English above). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 95...
The initializing procedure will start, and is completed when the message «Completed» is shown in the display. To return the System Menu, press the Close Window button. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 96...
1 SHOW STATUS 2 DISABLE 3 ENABLE 4 SYSTEM 5 SERVICE To select SYSTEM, press 4. To select CANCEL INHIBITED POINTS, press 7. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 97...
To select, press the relevant number (1-3): 1. Start 2. Stop 3. Show Running TImers Press Comments: The initializing procedure will start, and is Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 98...
It is possible to override the automatic day / night operation from the control panel by stopping the Day / Night Timers, and then issuing Enable / Disable Immediate Output Actioning commands manually. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 99...
14.2 Service Menu The Service Menu includes the following submenus: Note that the Oil&Gas Commands apply only to oil&gas systems. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 100...
(as shown in the example below). The zones in test mode are also shown. 19:23 TEST 19:23 Total: 1 1 OFFICES Total: 1 1:SHOW POINTS Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 101...
Page 102
To enter the Main Menu, press the Menu button 19:23 MENU Total: 3 1 SHOW STATUS 2 DISABLE 3 ENABLE 4 SYSTEM 5 SERVICE Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 102...
Page 103
To select a Zone Name, press CANTEEN CANTEEN KITCHEN KITCHEN OFFICES OFFICES WORKSHOP WORKSHOP then scroll downwards or upwards by pressing Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 103...
Page 104
8 OIL & GAS COMMANDS To select TEST, press 1. SERVICE 19:23 TEST 1 DETECTION ZONE TEST (EN 54) 2 OUTPUT TEST Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 104...
Page 105
To ensure that all selected detection zones leave Test Mode after carrying out this procedure, press the reset button on the front panel. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 105...
1 TEST 2 LOG 3 LOOP COMMANDS 4 REPORT 5 UPGRADE 6 REMOTE ACCESS 7 DUAL SAFETY 8 OIL & GAS COMMANDS Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 106...
Page 107
To select the Alarm Zone Name, press ATTIC ATTIC GROUND FLOOR GROUND FLOOR HOUSE HOUSE then scroll downwards or upwards by pressing Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 107...
Page 108
The test signal is given the lowest priority. In the event of an alarm, the alarm signal will thus override the test signal. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 108...
Page 109
8 OIL & GAS COMMANDS To select TEST, press 1. SERVICE 19:23 TEST 1 DETECTION ZONE TEST (EN 54) 2 OUTPUT TEST Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 109...
Page 110
2 FIRE ALARM ROUTING EQUIPMENT 3 FIRE WARNING ROUTING EQUIPMENT 4 OTHER OUTPUTS A test signal will be sent to the selected Fire Protection Equipment. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 110...
Page 111
8 OIL & GAS COMMANDS To select TEST, press 1. SERVICE 19:23 TEST 1 DETECTION ZONE TEST (EN 54) 2 OUTPUT TEST Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 111...
Page 112
2 FIRE PROTECTION EQUIPMENT 2 FIRE PROTECTION EQUIPMENT 3 FIRE WARNING ROUTING EQUIPMENT 3 FIRE WARNING ROUTING EQUIPMENT 4 OTHER OUTPUTS 4 OTHER OUTPUTS Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 112...
Page 113
Fire Alarm Devices. For detailed description, refer to 14.3.2.7. NOTE: When the test is terminated, make sure that all extinguishers or other similar equipment are properly connected. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 113...
Tests All Events All Events Log Setup Log Setup Read Parameters Read Parameters Read Filter Read Filter Clear Log Clear Log Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 114...
Page 115
Date, time and identity of all manually initiated tests. • All Events All events • Log Setup Read parameters, read filter, clear log. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 115...
3: READ BACKWARD 2: READ FORWARD 2: READ FORWARD To return to the previous page, use Action Digit 3 (READ BACKWARD). Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 118...
Filter are reset to default values. Clear Log This menu selection allows you to clear the entire Log Menu for all events previously recorded. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 119...
Page 120
From Date (YYYYMMDD) Continue Continue Time (hhmmss) Time (hhmmss) From time From time Read Direction Read Direction Number of Entries Number of Entries Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 120...
Page 121
1 READ PARAMETERS 2 READ FILTER 2 READ FILTER 3 CLEAR LOG 3 CLEAR LOG To enter READ FILTER, go to step 5b. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 121...
Page 122
Unit Type: Detection Zone Detection Zone Unit Name: Unit Name: Canteen Canteen Unit State: Unit State: Normal Normal Set filter Set filter Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 122...
To select DISABLE LOOP, press 1. 19:23 SERVICE DISABLE LOOP BSB 310 BSJ 310 BSL 310 Use the keyboard to enter text into the input box Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 124...
Page 125
Display Indication OR ,- as shown in this example: To select a Loop Name, press then scroll downwards or upwards by pressing Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 125...
Use the keyboard to enter text into the input box OR ,- as shown in this example: To select a Loop Name, press then scroll downwards or upwards by pressing Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 126...
3 LOOP COMMANDS 4 REPORT 5 UPGRADE 6 REMOTE ACCESS 7 DUAL SAFETY 8 OIL & GAS COMMANDS To select REPORT, press 4 Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 127...
Page 128
BSL-310 board), the Fire Alarm Control Panel’s name and its address, and finally the exact time and date when SelfVerify failed for this point. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 128...
To select Polluted, press 2 19:23 SERVICE REPORT POLLUTED 1 Heat Detector1 4: PRINT Comments: In this example one detector has been reported as polluted Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 129...
To enter the Main Menu, press the Menu button 19:23 MENU Total: 3 1 SHOW STATUS 2 DISABLE 3 ENABLE 4 SYSTEM 5 SERVICE To select SERVICE, press 5. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 130...
…..continued from step 2 in previous chapter . To select REPORT, press 4 To select VIEW SV REPORT STATUS, press 3 Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 131...
Enter the menu “View Upgrade Status” to follow the progress and verify that the procedure is completed. For detailed information on Upgrading procedures, refer to Commissioning Handbook. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 132...
6 REBOOT SYSTEM To select UPGRADE SW, press 1. Comments: The message “SW Upgrade in progress” is shown in the display. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 133...
6 REBOOT SYSTEM To select UPGRADE CONFIG, press 2. Comments: The message “Config Upgrade in progress” is shown in the display. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 134...
6 REBOOT SYSTEM To select EXPORT CONFIG, press 3. Comments: The message “Config export in progress” is shown in the display. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 135...
6 REBOOT SYSTEM To select EXPORT LOG press 4. Comments: The message “Log export in progress” is shown in the display. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 136...
To select REMOTE ACCESS, press 6. To select WEB ACCESS ON, press 1, then To select WEB ACCESS OFF, press 2, then Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 139...
DUAL SAFETY 1 SHOW STATUS 2 DISABLE 1 TRANSFER TO PRIMARY 3 ENABLE 2 TRANSFER TO SECONDARY 4 SYSTEM 5 SERVICE Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 140...
Page 141
Blinking light: the panel does not control all detection loops/loop units, and/or loop control is being transferred. Actions must be taken. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 141...
5 UPGRADE 6 REMOTE ACCESS 7 DUAL SAFETY 8 OIL & GAS COMMANDS To select OIL & GAS COMMANDS, press 8. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 142...
Page 143
Min.: Min.: Enter hours, then press Enter minutes, then press To execute the command (accept the inhibit time), press once more Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 143...
SERVICE CANCEL INHIBIT POINT CANCEL INHIBIT POINT 1ab12 1ab12 1mc3 1mc3 1mc6 1mc6 1od1 1od1 1od2 1od2 1od4 1od4 1od5 1od5 Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 144...
Page 145
To accept the selected point, press 19:23 SERVICE CANCEL INHIBIT POINT 1ab12 Execute cmd. To execute the command, press Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 145...
To select OIL & GAS COMMANDS, press 8. To select SET ALARM LIMITS, press 3. 19:23 SERVICE SET ALAR M LIMITS Name: Gas Detector Interface Type: Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 146...
Page 147
SET ALAR M LIMITS Name: Gas Detector Interface Type: SimradGD10P IR Value: EU: Status: Lo w: H igh: No rmal 40 Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 147...
To select OIL & GAS COMMANDS, press 8. To select GET MEASUREMENT VALUES, press 19:23 SERVICE GET MEASUREMENT VALU ES Name: Gas Detector Interface Type: Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 148...
Page 149
Type: SimradGD10P IR Value: Use keyboard, press Use keyboard, press To execute the command (accept the measurements for the point), press Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 149...
The Autronica communication protocol between AutroSafe and AutroMaster or other third party systems. AutroFieldBus The Autronica serial interface and low level protocol for field devices (loop controllers and power units / AutroSafe). AutroKeeper A unit that controls the Loop Driver’s access to the loop.
Page 151
Point A detector or a manual call point. PowerLoop The Autronica loop communication protocol for high power gas and flame detectors. 2-wire loop for both power and communication. Primary System The AutroSafe system that is designed to be in Active mode during normal operation (see Dual Safety).
The Detection Zone will be the trigger to generate outputs to the Alarm Zone. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 152...
Day / Night Operation. An Operation Zone given these properties and necessary parameter settings is referred to as a Day / Night Operation Zone. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 153...
The entire building, controlled and monitored by a Fire Alarm Control Panel (operator panel), is defined as an Operation Zone, Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 154...
• Available when the selected event is a enable the disablement. ENABLE disablement. Continues on next page… Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 155...
Page 156
The T1 delay period is started when a Fire Alarm signal from a point is received. Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 156...
Appendix 15.4 Menu Structure Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 157...
Page 158
Appendix Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19, Autronica Fire and Security AS Page 158...
Page 159
United Technologies Corporation (UTC) and employs more than 380 people with great skill and experience in the developing, manufacturing and marketing of fire safety equipment. Autronica Fire and Security AS is an international company based in Trondheim, a dynamic city known as the technological hotspot of Norway.