139548-N GF 400 DV IPI 7/21
Co-linear Vent Installation
The GF 400 DV IPI may be vented through a masonry or
Class A prefabricated chimney using a Co-linear Flexible
Vent system approved for use with a solid-fuel burning
fireplace. When installed in the manner described below,
this system can improve the performance of the appli-
ance in cold climate situations, as well as simplify the
vent installation. See figs. 11 and 13.
Consult with the local code authority having jurisdic-
tion before proceeding with this type of installation.
Refer to the vent manufacturer's instructions for specific
installation requirements.
These installation requirements must be followed:
1. Use the guidelines for vertical termination
on page 9.
2. Prior to the installation the chimney flue must be thor-
oughly cleaned and inspected by a qualified chimney
service person.
3. In a masonry chimney, a fireclay liner must be present
the entire length of the chimney.
4. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm).
5. No appliance can be installed into a chimney flue serv-
ing any other appliance of any kind.
6. THE AIR INTAKE FLEX PIPE MUST EXTEND 6 FEET BE-
YOND THE DAMPER AREA OF THE FIREPLACE.
7. If the intake flex duct does not extend the full length
of the chimney and connect to both the unit and the
termination cap, A METAL BLOCK OFF PLATE MUST
BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT
PRIOR TO THE END OF THE INTAKE FLEX AND MUST
COMPLETELY SEAL THE CHIMNEY FLUE FROM THE
ROOM.
If there is enough vent length and room in the flue,
adding a return loop in the air intake run will help pre-
vent draft reversals that can cause cold start problems.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS
OR FAILURE TO USE ONLY PARTS SPECIFICALLY AP-
PROVED FOR USE WITH THIS APPLIANCE MAY RESULT
IN PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE
TO MAINTAIN THE CLEARANCES TO COMBUSTIBLES
SPECIFIED IN THIS MANUAL AND IN THE INSTRUC-
TIONS PROVIDED WITH EACH VENT COMPONENT.
NOTE: THIS VENT CONFIGURATION MAY REQUIRE THE
APPLIANCE BE OPERATED IN CPI MODE TO ASSURE
ADEQUATE DRAFT AND PROPER PERFORMANCE.
11
Exhaust Gas
Max. Co-linear
Height - 35 ft.
(10.66 m)
Min. Co-linear
Height - 10 ft.
(3.05 m)
The chimney
must be sealed
off from the
room by a steel
plate at the
damper area.
Figure 11. Co-linear Adaptor installed through a masonry
chimney. Components shown may differ somewhat from
manufacturer to manufacturer.
Figure 12. Simpson Dura-Vent #923GCL Co-linear Adaptor
is shown - other manufacturer's components may differ.
Subtract 2 1/4" for Short Legs.
High Wind Cap
Intake Air
The Air
Intake Flex
pipe must
extend
beyond the
damper.
Dual 3"Flex
Liners
Max. offset
24"
(609 mm)
29"
to top of
Co-linear
25 1/2"
Adapter
to center
of flue collar