5. Inspection – storage
5.1. Upon receipt of the model immediately check its state of integrity; immediately dispute with the transport
company any damage. The packaging is created according to the model, to the suitable means of transport
and of handling.
5.2. Condenser exchangers (PKE condensers) and gas coolers (PKE CO2) are supplied with a dry air preload at 2
bar and have charge connections UNF 7/16"-20. Check for the presence of pressure. In the absence of
pressure, contact the Manufacturer immediately and report the problem on the transport document. Insufficient
pressure indicates a loss due to damage incurred during transportation.
5.3. The model must be stored in its original packaging in a place that is protected and away from weathering.
5.4. Do not stack any other material on the packaging.
5.5. If stacking of the unit is permitted, follow the instructions on the packaging.
5.6. Apply the following rules when the unit must remain in storage for long periods of time. The unit must be stored
inside, oriented according to its work position. This ensures functionality of the fan drainage holes. With the
unit stored in a damp environment, it is necessary to examine the outer covering to make sure that there are no
damaged points. If any are found, have them repainted. The fans must be protected with reinforced plastic
sheets or other mechanical protection against water and/or contaminants, which could damage them. The free
surface of the finned pack must be mechanically protected with a panel or with something similar. During
storage, the fans must be manually rotated at least once every 3 months.
5.7. If stored for a long time, remove condensed moisture by turning on the unit for at least two hours per month.