8.3. Power supply 230V 50 Hz – EC motor
8.4. Before using speed adjustment systems, check their compatibility with the fan motors. Incompatible systems
can generate noise and damage. The Manufacturer assumes no responsibility for the performance of models
equipped with adjustment systems.
8.5. For other connections refer to the diagram printed on the inside of the motor-fan box.
8.6. In fan motors equipped with thermocontacts (TK), they must be connected to the control circuit.
8.7. In the models supplied with the wiring in the junction box, remove the side cover to make the connection.
www.modine.com
 
Symbol on fan
Function
motor
PE
Earthing
N, L
Power supply, 50 Hz
NC
Floating status contact, fault opening
COM
Floating state contact, switching contact, common
connection (2A, max 250 VAC, min. 10 mA, AC1)
NO
Floating status contact, fault closure
OUT
Analog output, 0-10 VDC, max 3 mA, SELV,
output of the current motor modulation level:
1 V corresponds to 10% modulation
10 V corresponds to 100% modulation
GND
Earth interface control reference, SELV
0...10 V
Control input / value of input current sensor 0-10
VDC, impedance 100 kΩ only as an alternative to
input 4...20 mA, SELV
+10 V
Fixed voltage output 10 VDC (±3%), max. 10 mA,
power supply for external devices (e.g.
potentiometer), SELV
+20 V
Fixed voltage output 20 VDC (+25% / -10%), max.
50 mA, power supply for external devices (e.g.
sensors), SELV
4...20 mA
Control input / value of the input current sensor
4...20 mA, impedance 100 kΩ only as an
alternative to input 0...10 V, SELV
RSB
RS485 interface for ebmBUS, RSB, SELV
RSA
RS485 interface for ebmBUS, RSB, SELV
30