8.8. It is mandatory to use minimum section power cables as indicated (see Table 1 – Minumum cable section).
Refer to the technical standards in force in the country of installation, also according to the laying methods and
length of the cables and their type.
8.10. To minimise the risk due to indirect contacts, the electrical system can be earthed by means of the pin located
under the side cover, next to the junction box.
8.11. Attention: The fan motors are equipped with self-resetting internal protective thermocouples.
8.12. For further information refer to the diagrams supplied with the model.
www.modine.com
Table 1 – Minimum cable selection
Rated current (A)
11
15
20
26
36
48
64
80
95
150
170
2
Power cord section (mm
1,5
2,5
4
6
10
16
25
35
50
95
120
)