Occupancy/Vacancy Sensors offer a Walk Test mode which shortens the
vacancy timer to 10 seconds, allowing for simple and quick verification of the
sensors coverage and range in the installed space.
Walk-Test mode automatically exits and the
sensor returns to normal operation after 5
minutes and can be manually terminated early by
pressing the [Walk Test] button.

Enable Walk Test Mode

Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Echo Occupancy/Vacancy Sensor
Occupancy/Vacancy Sensor
Prepare the site for configuration.
a: Make certain the sensor and lighting loads are powered
and connected for control by the Echo controller.
b: You will need direct access to the Occupancy/Vacancy
Sensor in order to place it into Walk Test mode.
Press the [Walk Test] button on the front of the sensor to
enable the Walk Test feature at the sensor. A green LED will
begin to flash, indicating Walk Test is enabled and the
vacancy/no vacancy occupancy timer will be shortened to 10
seconds.
Move throughout the space including corners and areas that
may specifically be obscured from line of sight to the sensor.
Each time the sensor detects movement, the lens will
illuminate red.
Adjust the lens masking, if installed, blocking certain areas of
the installed space from sensor detection. See
on page 10.
Walk Test mode will automatically exit after five minutes from
the time it was enabled. To manually exit the Walk Test mode,
press either of the buttons on the sensor.