Range Confirmation Test - ETC echoflex MOS-IR A Series Installation Manual

Ceiling-mount occ/vac sensor
Hide thumbs Also See for echoflex MOS-IR A Series:
Table of Contents

Advertisement

Echoflex Installation Guide
Ceiling-Mount Occ/Vac Sensor (MOS)
Tests and Settings
The [Teach] button and color LEDs (green, blue, and red) are used to
navigate the tests and settings menu:
• Light Level Test

• Range Confirmation Test

• Walk Test
• Sensor Setting Mode
• Change LED Display
Note:
Light Level Test
The Light Level Test verifies the energy produced by the solar panels.
1. Press and hold the [Teach] button until the green LED starts blinking.
2. Press and hold the [Teach] button again until the green LED stops
blinking. The green LED then repeats a number of blinks according to
the detected light level (see table below).
Blinks
0
1
2
3
4
5
The time to fully charge the storage capacitor is from a non-operational
condition. Discharge time indicates how long a fully charged sensor
operates in the dark. The test repeats every two seconds and runs for 100
seconds. To exit before the time-out, press and hold the [Teach] button.
Range Confirmation Test
The Range Confirmation Test verifies the wireless signal strength with a
linked controller that has range confirmation capability.
Note:
1. Press and hold the [Teach] button until the green LED starts blinking.
Ceiling-Mount Occ/Vac Sensor (MOS)
Some older devices have an amber LED in place of blue.
Lux (Footcandles)
0 (0)
20 to 40 (2 to 4)
40 to 80 (4 to 8)
80 to 160 (8 to 16)
160 to 320 (16 to 32)
320+ (32+)
The sensor must be fully charged or use a battery to run
the test. Only one controller can be linked to the sensor
to run the test properly. Disable repeaters in range.
Page 5 of 8
Time to Fully
Charge
non-operational
operational
48 hours
24 hours
12 hours
6 hours
Discharge
Time
n/a
n/a
100 hours
150 hours
200 hours
225 hours