Mitsubishi Electric MELSEC-A0J2H Series Handbook page 43

Table of Contents

Advertisement

3
I/O MODULES REPLACEMENT
A0J2H models to be discontinued
Product name
Input module
Output module
Model name
Model name
A0J2E-E32D
QX80
*1
QY10
A0J2-E24R
*1
QY10
A0J2E-E24R
*1
QY22
A0J2-E24S
Alternative Q series models
Remarks (restrictions)
1) Change in external wiring: Required
2) Change in the number of modules: Required
(2 modules necessary)
3) Change in a program
Change in the number of occupied I/O points: Required (64
points  16 points × 2)
4) Change in specifications
Change in rated input voltage: Required (12VDC not
*2
applicable)
Change in rated input current: Required (Approx. 7mA 
Approx. 4mA)
Change in ON voltage/ON current: Required
Change in OFF voltage/OFF current: Required
Change in input resistance: Required
5) Change in functions: Not required
1) Change in external wiring: Required
2) Change in the number of modules: Required
(2 modules necessary)
3) Change in a program
Change in the number of occupied I/O points: Required (64
points  16 points × 2)
4) Change in specifications
Change in rated output voltage: Not required
Change in rated output current: Not required
(Note that a contact life is half.)
5) Change in functions: Not required
1) Change in external wiring: Required
2) Change in the number of modules: Required
(2 modules necessary)
3) Change in a program
Change in the number of occupied I/O points: Required (64
points  16 points × 2)
4) Change in specifications
Change in rated output voltage: Not required
Change in rated output current: Not required
(Note that a contact life is half.)
5) Change in functions: Required (without varistor, fuse)
1) Change in external wiring: Required
2) Change in the number of modules: Required
(2 modules necessary)
3) Change in a program
Change in the number of occupied I/O points: Required (64
points  16 points × 2)
4) Change in specifications
Change in rated output voltage: Not required
Change in rated output current: Not required
5) Change in functions: Required (without fuse)
3
- 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents