Mitsubishi Electric MELSEC-A0J2H Series Handbook page 227

Table of Contents

Advertisement

Specifications
A0J2-E56AS output specifications
CR
Surge
absorber
suppressor
Varistor
Common terminal
8 points/common
arrangement
(Common terminal: TB9, TB19, TB29)
Operation indication
(Turning ON the input turns LED ON)
Specifications
5VDC internal current
460mA (TYP. All points are ON.)
consumption
External
Voltage
supply
power
(Module
power
Current
supply)
External connection
36-point terminal block connector
method
(M3 × 6 screws) 2 pieces
Applicable wire size
(Applicable tightening torque 69N•cm)
1.25-3, 1.25-YS3A, 2-S3,
Applicable solderless
2-YS3A, V1.25-3, V1.25-YS3A,
terminal
Weight
External dimensions
250(H) × 190(W) × 41(D) mm
*1
Check that the specifications of leakage current of the used sensor and switches are equal to or less than the OFF current
value.
If leakage current is equal to or more than the OFF current specifications, take measures against it with referring to "Input
Module Troubleshooting" in the following handbook.
(Handbook for replacement)
Renewal tool for A0J2 series Transition from MELSEC-A0J2(H) series to renewal system using renewal tool (refer to
Appendix 3.5.)
*2
The value when using the input module, QX41Y41P, QX41, etc. and 5ms is set at input response time in I/O assignment
setting of PLC parameter (10ms is set at default).
*3
The figure below shows the temperature derating chart.
*4
The value when using the output module,QX41Y41P, QY41P, etc.
*5
The weight of fixed stand of programmable controller depends on replacement type of renewal tool for A0J2.
*6
The external dimensions of the SC-A0JQIF56AS do not include those of its projection.
SC-A0JQIF56AS output
0.022µF+47
None
(Common terminal: TB9, TB19, TB29)
Available
A0J2-E56AS
None
Ripple voltage 4Vp-p or less
None
36-point terminal block connector
(M3 × 6 screws) 2 pieces
2
0.75 to 2mm
(Applicable tightening torque 69N•cm)
1.25-3, 1.25-YS3A, 2-S3,
2-YS3A, V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
1.10kg
182(H) × 190(W) × 41(D)mm
(A)
0.6
0.5
0.4
Output load
current
0.3
0.2
0.1
30
Compatibility
specifications
0.015µF+22
Varistor (400 to 540V)
8 points/common
None
SC-A0JQIF56AS
Compatibility
24VDC ±10%
580mA
2
0.75 to 2mm
V2-S3, V2-YS3A
0.66kg
*6
40
50
55 (­)
Ambient temperature
Precautions for replacement
Operation indication can be checked
with Q series input module.
Precautions for replacement
To deliver a power for programmable
controller operation, connecting a
×
module power supply to the interface
module, TB35 or TB36 is required.
If the voltage exceeds existing power
×
capacity, add 24VDC power supply
separately.
Also consider the weight of fixed stand
of programmable controller.
Check the dimensions since they
×
depend on the installation type
(building-up/horizontal/separate type).
*5
App
- 32