Specifications
5VDC internal current
consumption
External
supply
Voltage
power
(Module
power
Current
supply)
External connection
36-point terminal block connector
method
Applicable wire size
(Applicable tightening torque 69N•cm)
Applicable solderless
terminal
Weight
External dimensions
*1
The figure below shows the derating chart.
*2
Check that the specifications of leakage current of the used sensor and switches are equal to or less than the OFF current
value.
If leakage current is equal to or more than the OFF current specifications, take measures against it with referring to "Input
Module Troubleshooting" in the following handbook.
(Handbook for replacement)
Renewal tool for A0J2 series Transition from MELSEC-A0J2(H) series to renewal system using renewal tool.
*3
The value when using the input module, QX41Y41P, QX41, etc. and 5ms is set at input response time in I/O assignment
setting of PLC parameter (10ms is set at default).
*4
The value when using the output module, QX41Y41P, QY41P, etc.
*5
The weight of fixed stand of programmable controller depends on replacement type of renewal tool for A0J2.
*6
The external dimensions of the SC-A0JQIF28AR do not include those of its projection.
App
- 17
A0J2-E28AR
140mA (TYP. All points are ON.)
None
None
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A, 2-S3,
2-YS3A, V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.68kg
250(H) × 132(W) × 41(D)mm
(%)
100
90
80
Simultaneous ON
70
ratio at AC input
60
50
40
30
SC-A0JQIF28AR
24VDC±10%
Ripple voltage 4Vp-p or less
105mA
36-point terminal block connector
(M3 × 6 screws)
2
0.75 to 2mm
(Applicable tightening torque 69N•cm)
1.25-3, 1.25-YS3A, 2-S3,
2-YS3A, V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.44kg
*6
182(H) × 132(W) × 41(D)mm
26.4VDC
External power supply
(module power supply)
40
50 55 (­)
Ambient temperature
: Compatible,
: Partially changed, × : Incompatible
Compatibility
Precautions for replacement
To deliver a power for programmable
controller operation, connecting a
×
module power supply to the interface
module, TB35 or TB36 is required.
If the voltage exceeds existing power
×
capacity, add 24VDC power supply
separately.
Also consider the weight of fixed stand
of programmable controller.
Check the dimensions since they
×
depend on the installation type
(building-up/horizontal/separate type).