Mitsubishi Electric MELSEC-A0J2H Series Handbook page 223

Table of Contents

Advertisement

(12)Specifications comparison between A0J2-E56AR and interface module (SC-
A0JQIF56AR)
Specifications
A0J2-E56AR input specifications
Number of input points
Insulation method
Rated input voltage
100 to 120VAC 50/60Hz
Rated input current
10mA (100VAC 60Hz)
Operating voltage range
85 to 132VAC (50/60Hz±5%)
Maximum number of
60% (10 points/common)
simultaneous input
simultaneously ON
points
ON voltage/ON current
80VAC or more/6mA or more
OFF voltage/OFF
40VAC or less/4mA or less
current
Maximum 300mA,
Inrush current
Within 0.3ms (132VAC)
Approx. 10k (60Hz),
Input impedance
Approx. 12k (50Hz)
OFFON
15ms or less (6ms TYP.)
Response
time
ONOFF
35ms or less (16ms TYP.)
Common terminal
16 points/common
arrangement
(Common terminal: TB17, TB34)
Operation indication
(Turning ON the input turns LED ON)
SC-A0JQIF56AR input
32 points
Photocoupler
100 to 120VAC 50/60Hz
10mA (100VAC 60Hz)
85 to 132VAC (50/60Hz±5%)
60% (10 points/common)
80VAC or more/6mA or more
26VAC or less/1.7mA or less
Within 0.3ms (132VAC)
Approx. 10k (60Hz),
Approx. 12k (50Hz)
(Common terminal: TB17, TB34)
Available
: Compatible,
Compatibility
specifications
32 points
Photocoupler
simultaneously ON
Maximum 300mA,
14ms or less
(11ms TYP.)
19ms or less
(13ms TYP.)
16 points/common
None
: Partially changed, × : Incompatible
Precautions for replacement
*1
OFF voltage/OFF current is smaller.
In combination with Q series input
module:
*2
15ms or less (12ms TYP.)
In combination with Q series input
module:
*2
20ms or less (14ms TYP.)
Operation indication can be checked
with Q series input module.
App
- 28

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents