Mitsubishi Electric MELSEC-A0J2H Series Handbook page 102

Table of Contents

Advertisement

3
I/O MODULES REPLACEMENT
Specifications
Number of output points
Insulation method
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at
ON
OFFON
Response
time
ONOFF
External
Voltage
supply
power
Current
Surge suppressor
Fuse
Fuse blown indication
Protection function
Protection function reset
Common terminal
arrangement
Operation indication
Specifications
Current consumption
External connection
method
Applicable wire size
Applicable solderless
terminal
External dimensions
Weight
*1
Use the QX70 when using 12VDC.
*2
Check the specifications of the sensor or switches to be connected to the QX80.
*3
The fuse blown is not detected when the external power supply is off.
3
- 61
A0J2E-E56DT output
specifications
24 points
Photocoupler
12/24VDC
10.2 to 26.4VDC
0.8A/1 point, 0.8A/1 point
(60% ON, 55°C)
No restriction (Short protect)
1.0mA or less
1.0V (TYP.) 0.8A,
1.5V (MAX.) 0.8A
0.5ms or less
1.5ms or less
(Rated load, resistance load)
12/24VDC
(10.2 to 30VDC)
200mA
(24VDC, All points are ON.)
Surge absorbing diode
Available (When a fuse blown
occurs, LED is lit, and a signal is
Available (overheat protection
and short circuit protection)
Overheat protection: activated to
two points
Automatic reset
(by deactivating overheat
protection function)
8 points/common
(Common terminal: TB9, TB19,
TB29)
Available (Turning ON the output
turns LED ON)
A0J2E-E56DT
0.225A (TYP. All points are ON.)
36-point terminal block
connector
(M3 × 6 screws) 2 pieces
2
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
(Sleeved solderless terminals
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
250(H) × 190(W) × 41(D)mm
98(H) × 27.4(W) × 90(D)mm × 4
1.08kg
: Compatible,
QY80
Compatibility
16 points
Photocoupler
12 to 24VDC
10.2 to 28.8VDC
0.5A/1 point, 4A/1 common
4A 10ms or less
0.1mA or less
0.2VDC (TYP.) 0.5A,
0.3VDC (MAX.) 0.5A
1ms or less
1ms or less
12 to 24VDC (+20/-15%)
(Ripple ratio within 5%)
20mA (During 24VDC)
Zener diode
6.7A (Not exchangeable)
(Fuse blown capacity: 50A)
*3
output to the CPU)
16 points/common
(Common terminal: TB17)
ON indication (LED)
QX80/QY22
Compatibility
0.05 × 2 + 0.08 × 2 = 0.26A
(TYP. All points are ON.)
18-point terminal block
(M3 × 6 screws)
1 piece/module
2
0.3 to 0.75mm
core
(Outside diameter: 2.8mm or
less)
R1.25-3
cannot be used.)
0.16 × 2 + 0.17 × 2 = 0.66kg
: Partially changed, × : Incompatible
Precautions for replacement
When seventeen or more points
are used, use two QY80s.
The maximum load current per
point is smaller. Use caution on
selecting the load to use.
The inrush current value differs.
Use caution on selecting the load
to use.
The response times differ.
Voltages exceeding 28.8VDC
cannot be applied.
The QY80 has the fuse instead of
overheat and short circuit
protection function.
×
As the common changes from
three commons to a common,
wiring with a different voltage for
each common is not possible.
Precautions for replacement
Review current capacity since
current consumption is increased.
×
×
Wiring change is required.
×
×
The dimensions are different.