Mitsubishi Electric MELSEC-A0J2H Series Handbook page 220

Table of Contents

Advertisement

Specifications
A0J2-E28DS input specifications
CR
Surge
absorber
suppressor
Varistor
Common terminal
arrangement
Operation indication
(Turning ON the input turns LED ON)
Specifications
5VDC internal current
consumption
External
Voltage
supply
power
(Module
power
Current
supply)
External connection
36-point terminal block connector
method
Applicable wire size
(Applicable tightening torque 69N•cm)
Applicable solderless
terminal
Weight
External dimensions
*1
The value when using the input module, QX41Y41P, QX41, etc. and 5ms is set at input response time in I/O assignment
setting of PLC parameter (10ms is set at default).
*2
The value when using the output module, QX41Y41P, QY41P, etc.
*3
The weight of fixed stand of programmable controller depends on replacement type of renewal tool for A0J2.
*4
The external dimensions of the SC-A0JQIF28DS do not include those of its projection.
App
- 25
0.022µF+47
None
8 points/common
(Common terminal: TB26)
4 points/common
(Common terminal: TB33)
Available
A0J2-E28AS
260mA (TYP. All points are ON.)
None
None
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A, 2-S3,
2-YS3A, V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.65kg
250(H) × 132(W) × 41(D) mm
SC-A0JQIF28DS input
specifications
0.015µF+22
Varistor (400 to 540V)
8 points/common
(Common terminal: TB26)
4 points/common
(Common terminal: TB33)
None
SC-A0JQIF28AS
24VDC ± 10%
Ripple voltage 4Vp-p or less
285mA
36-point terminal block connector
(M3 × 6 screws)
2
0.75 to 2mm
(Applicable tightening torque 69N•cm)
1.25-3, 1.25-YS3A, 2-S3,
2-YS3A, V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.41kg
*4
182(H) × 132(W) × 41(D)mm
Compatibility
Precautions for replacement
Operation indication can be checked
with Q series input module.
Compatibility
Precautions for replacement
To deliver a power for programmable
controller operation, connecting a
×
module power supply to the interface
module, TB35 or TB36 is required.
If the voltage exceeds existing power
×
capacity, add 24VDC power supply
separately.
Also consider the weight of fixed stand
of programmable controller.
Check the dimensions since they
×
depend on the installation type
(building-up/horizontal/separate type).
*3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents