Specifications
A0J2-E28AR output specifications
Number of output points
Insulation method
24VDC 2A (Resistance load)/point
Rated switching voltage/
240VAC 2A (COS=1)/point
current
Minimum switching load
Maximum switching
264VAC 125VDC
voltage
Maximum switching
frequency
Mechanical life
20 million times or more
Rated switching voltage/current load
200,000 times or more
200VAC 1.5A, 240VAC 1A
(COS=0.7) 200,000 times or more
Electrical life
200VAC 0.75A, 240VAC 0.5A
(COS=0.35) 200,000 times or more
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 200,000 times or more
OFFON
Response
time
ONOFF
External
Voltage
supply
Ripple voltage 4Vp-p or less
power
(Relay coil
Current
driving
(24VDC All points are ON.)
power)
Surge suppressor
8 points/common
(Common terminal: TB26)
Common terminal
3 points/common
arrangement
(Common terminal: TB31)
(Common terminal: TB31)
Operation indication
(Turning ON the output turns LED ON)
Fuse rating
Fuse blown indication
Relay socket
SC-A0JQIF28AR output
12 points
Photocoupler
24VDC 2A (Resistance load)/point
240VAC 2A (COS=1)/point
5A/common
5VDC 1mA
3600 times/hr
20 million times or more
Rated switching voltage/current load
200,000 times or more
200VAC 1.5A, 240VAC 1A
(COS=0.7) 200,000 times or more
200VAC 0.75A, 240VAC 0.5A
(COS=0.35) 200,000 times or more
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 200,000 times or more
10ms or less
12ms or less
24VDC±10%
Ripple voltage 4Vp-p or less
125mA
(24VDC All points are ON.)
None
(Common terminal: TB26)
(Common terminal: TB31)
independent
(Common terminal: TB31)
Available
None
None
: Compatible,
Compatibility
specifications
12 points
Relay isolation
5A/common
5VDC 1mA
264VAC 125VDC
3600 times/hr
9ms or less
11ms or less
24VDC±10%
125mA
None
8 points/common
3 points/common
independent
None
None
None
: Partially changed, × : Incompatible
Precautions for replacement
In combination with Q series output
module:
*4
10ms or less
In combination with Q series output
module:
*4
12ms or less
Operation indication can be checked
with Q series output module.