Mitsubishi Electric MELSEC-A0J2H Series Handbook page 100

Table of Contents

Advertisement

3
I/O MODULES REPLACEMENT
Specifications
OFFON
Response
time
ONOFF
Surge suppressor
Fuse rating
Fuse blown indication
Common terminal
arrangement
Operation indication
Specifications
Current consumption
External connection
method
Applicable wire size
Applicable solderless
terminal
External dimensions
Weight
*1
Consider the characteristics of the triac and observe the necessary precautions by referring to Section 3.3 (3) before
replacing the modules.
*2
Use the QX70 when using 12VDC.
*3
Check the specifications of the sensor or switches to be connected to the QX80.
*4
Install a fuse for each external terminal point to prevent the burnout of the external devices and modules during load shorts.
3
- 59
A0J2E-E56DS output
specifications
1ms or less
0.5 cycle + 1ms or less
(Rated load, resistance load)
CR absorber
(0.022µF + 47)
High speed type fuse 3.2A
(1/common) HP-32
Available (When a fuse blown
occurs, LED is lit, and a signal is
output to the CPU)
8 points/common
(Common terminal: TB9, TB19,
TB29)
Available (Turning ON the output
turns LED ON)
A0J2E-E56DS
0.46A (TYP. All points are ON.)
36-point terminal block
connector
(M3 × 6 screws) 2 pieces
2
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
(Sleeved solderless terminals
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
250(H) × 190(W) × 41(D)mm
98(H) × 27.4(W) × 90(D)mm × 4
1.08kg
: Compatible,
QY22
Compatibility
1ms or less
1ms + 0.5 cycle or less
CR absorber
16 points/common
(Common terminal: TB17)
ON indication (LED)
QX80/QY22
Compatibility
0.05 × 2 + 0.25 × 2 = 0.60A
(TYP. All points are ON.)
18-point terminal block
(M3 × 6 screws)
1 piece/module
2
0.3 to 0.75mm
core
(Outside diameter: 2.8mm or
less)
R1.25-3
cannot be used.)
0.16 × 2 + 0.40 × 2 = 1.12kg
: Partially changed, × : Incompatible
Precautions for replacement
×
*4
The fuse is not built in.
×
As the common changes from
three commons to a common,
wiring with a different voltage for
each common is not possible.
Precautions for replacement
Review current capacity since
current consumption is increased.
×
×
Wiring change is required.
×
×
The dimensions are different.
Be aware of that the weight
increases when calculating the
weight.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents