Digital Settings; Bacnet Setup; Address Switch; Technical Data - E+E Elektronik EE210 User Manual

Humidity and temperature transmitter for demanding climate control applications
Hide thumbs Also See for EE210:

Advertisement

DIGITAL SETTINGS

BACnet Setup

BACnet PICS are abvailable for download at

Modbus Setup

Address Switch

0 0 0 0 0 0 0 0
Address Switch
1 1 0 1 0 0 0 0
The measured values are saved as a 32 Bit float value from 0x19 to 0x1F and from 0x23 to 0x29. Additionally the measured values
are available as 16 Bit signed integer from 0x12C to 0x12F and from 0x131 to 0x134.
The factory setting for the Slave-ID (Modbus address) is 242 as an integer 16Bit value. This ID can be changed by the user in the
register 60001 (0x00), permitted values are 1 - 247 permitted.
The serial number as ASCII-code is located at register address 30001-30008 (16 Bit per address).
The Firmware version is located at register address 30009 (Bit 15...8 = major release; Bit 7...0 = minor release).
The choice of measurement units (metric or not metric) must be done in the ordering guide, see EE210 data sheet.
Switching from metric to non metric or vice versa by using the EE-PCS is not possible.
FLOAT (read register):
Register
Communication
address
address
30026
0x19
30028
0x1B
30030
0x1D
30032
0x1F
30036
0x23
30038
0x25
30040
0x27
30042
0x29
INFO (read register):
Register
Communication
address
address
30001
0x00
30009
0x08
Protocol setting:
Address, baudrate, parity and stop bits can be set via:
1. Product Configurator Software (available on www.epluse.com/EE210)
2. Modbus protocol (please see Application Note Modbus (available on www.epluse.com/EE210)

TECHNICAL DATA

(Modification rights reserved)

Measured Values

Relative Humidity (RH)
Sensor
Working range
RH accuracy (incl. hysteresis, non-linearity and repeatability)
Wall & duct version:
-15...40 °C (5...104 °F)
-15...40 °C (5...104 °F)
-40...60 °C (-40...140 °F)
Remote probe version
at 20 °C (68 °F)
www.epluse.com/EE210
0
Slave address setting via EE-PCS Product Configuration Software:
All switches at position 0 → address has to be set via Product Configuration Software
(factory setting 242).
1
Example: Slave address is set via configuration software.
0
Slave address setting via Dip-Switch:
Setting the Dip-Switch to any other address than 0 overwrites the slave address set
via configuration software.
1
Example: Slave address set to 11 (=00001011 binary).
Parameter
name
temperature
[°C], [°F]
relative humidity
[%]
water vapour partial pressure
[mbar], [psi]
dew point temperature
[°C], [°F]
absolute humidity
[g/m³], [g/ft³]
mixing ratio
[g/kg], [gr/lb]
specific enthalpy
[kJ/kg], [BTU/lb]
frost point temperature
[°C], [°F]
Parameter
name
Serial number (as ASCII)
Firmware version
E+E Sensor HCT01-00D
0...100 % RH
≤90 % RH
>90 % RH
INTEGER (read register):*
Register
Communication
address
address
30301
0x12C
30302
0x12D
30303
0x12E
30304
0x12F
30306
0x131
30307
0x132
30308
0x133
30309
0x134
* Values are stored with a scaling of 1:100 (e.g.: 2550 is equivalent to 25.5°C)
INTEGER (write register):*
Register
Communication
address
address
60001
0x00
60002
0x01
*For Modbus protocol setting please see Application Note Modbus
(www.epluse.com/EE210)
±(1.3 + 0.003*measured value) % RH
± 2.3 % RH
±(1.5 + 0.015*measured value) % RH
±2.5 % RH
Parameter
name
temperature
[°C], [°F]
relative humidity
[%]
water vapour partial pressure
[mbar], [psi]
dew point temperature
[°C], [°F]
absolute humidity
[g/m³], [g/ft³]
mixing ratio
[g/kg], [gr/lb]
specific enthalpy
[kJ/kg], [BTU/lb]
frost point temperature
[°C], [°F]
Parameter
name
Slave-ID (modbus addresse)
Modbus protocol settings*