5.8 Time bands

The operation of all the devices in the system can be controlled based on set time bands, managing the
status (STANDBY / ON) and if necessary setting a common set point.
The following are available:
2 common time bands for the first five days of the week (Monday-Friday)
2 common time bands for the last two days (Saturday-Sunday).
Information
Parameter En04 (Use clock and time bands) must be set to 1 (default value).
In the periods when the system is off, none of the e-drofan units can be started, not even using the
acqua or e-droset terminal, as the µAM keeps all the devices OFF by setting the status every minute.
In the periods when the system is on, the individual e-drofan units can be switched off, as the µAM does
not set the ON status.
In any case, sending the change in status from the µAM (POWER button or automatically when managed
by time bands) cancels and replaces the previous status for all the devices connected.
5.8.1 Setting the times and the actions
The time band menu displays the following, in sequence:
• time band 1 (HH)
for days 1 to 5;
• time band 1 (MM)
for days 1 to 5;
• time band 1 (ACTION)
for days 1 to 5;
• time band 2 (HH)
for days 1 to 5;
• time band 2 (MM)
for days 1 to 5;
• time band 2 (ACTION)
for days 1 to 5;
• time band 1 (HH)
for days 6 & 7;
• time band 1 (MM)
for days 6 & 7;
• time band 1 (ACTION)
for days 6 & 7;
• time band 2 (HH)
for days 6 & 7;
• time band 2 (MM)
for days 6 & 7;
• time band 2 (ACTION)
for days 6 & 7.
Procedure
1.
press CLOCK for 3 seconds: the display shows the symbols (10) for days 1 to 5 and, in field 15,
the number of the time band. Symbol 17 flashes, field 18 displays time band 1, the hours flash;
Important: if the CLOCK button is erroneously held for more than 5 seconds, clock setting procedure is
accessed; to exit, simply press CLOCK 3 times, then start again.
2.
set the desired value (0 to 23) using UP / DOWN;
3.
press CLOCK to set the minutes;
4.
press CLOCK to set the action for the time band: the main display 6 shows one of the following values:
• OFF: at the set time the µAM will switch all the devices in the system to STANDBY;
• ON: at the set time the µAM will switch all the devices in the system ON; the e-drofan units will
control the ambient conditions based on their own set point;
• A temperature set point value: at the set time the µAM will switch all the devices in the system ON
and will send the set point to all the e-drofan units; if Ch01=2 or Co01=2, the set point will override
the set point on the µAM (see par. "Using the µAM temperature set point";
use UP / DOWN to select: OFF, ON or a set point (8 to 32 °C with increases of 1 °C);
5.
press CLOCK to continue the settings for time band 2; only times after those set for time band 1 can
be set;
6.
for each setting, the following options are available:
continue to set the other time bands in the same way;
or press SLEEP to end, saving the settings;
or wait 1 minute without pressing any button: the procedure will end
automatically, saving the settings.