5.8.2 Activating / deactivating time band operation
Information
Time band operation cannot be activated if the action all four time bands is set to ON or OFF.
Procedure
1.
Make sure the operation of the system is activated (see the section "System ON / STANDBY").
2.
To activate / deactivate time band management, press CLOCK: symbol 17 comes on / goes off.
During time band operation:
• The display shows the operation of the system with symbols 1, 2 3, 4 or 5; if none of these symbols
is on, the system is in TEMPORARY STANDBY;
• Briefly pressing the ON button switches from ON to TEMPORARY STANDBY and vice-versa
("override" bands) until the next time band starts (in this case, OFF is not shown on the display);
• The mode set by the MODE button is not affected by time band operation.
3.
To switch the system to STANDBY (NON-TEMPORARY) hold the ON button until "OFF" is displayed;
4.
To restart the system, press the ON button: time band operation will be reactivated and the action
defined for the active band will be performed.
Additional information
After an extended power failure in which the clock settings are lost, the system will restart in ON mode, not
managed by time bands.

5.9 Alternative displays

The TEMP button, depending on the settings made during installation, can be used to display (and in
some cases set) the following values (note: 3 seconds after the last button is pressed, normal display mode
resumes automatically):
Display when
Configuration
Normal display
TEMP button
the FIRST time
µAM
µAM without
temperature
humidity probe
probe
Ch01≠2
and
Co01≠2
µAM
µAM without
temperature
humidity probe
set point
Ch01=2
or
Change using
Co01=2
UP/DOWN
µAM
temperature
µAM with
probe
humidity probe
Ch01≠2
and
Co01≠2
µAM
µAM with
temperature
humidity probe
set point
Ch01=2
or
Change using
Co01=2
UP/DOWN
+030220460 rel. 1.0 - 08.05.2007
µAM
Value displayed in the main field (6)
Display when
Display when
pressing the
pressing the
pressing the
TEMP button the
TEMP button
SECOND time
the THIRD time
µAM
temperature
probe
returns to
normal
display mode
µAM
humidity set
humidity
point
probe
(parameter
Hu01)
returns to
display mode
Change using
UP/DOWN
µAM
µAM
humidity
temperature
humidity
set point
probe
probe
(parameter Hu01)
Change using
UP/DOWN
Display when
pressing the
TEMP button the
FOURTH time
normal
returns to
normal
display mode
Tab. 5.a
27
Fig. 5.y