Fig. 24 Ks2000 - Addressing Of The Dali Device - Displaying The Physical Addressing - Beckhoff KL6811 Documentation

Dali/dsi master terminal with integrated power supply
Table of Contents

Advertisement

Configuration software KS2000
Do not interrupt the addressing process
The addressing procedure must not be interrupted by other DALI commands. Make sure of this by,
for instance, interrupting your PLC program or the K-Bus cycle before starting the addressing.
Sequence of actions for physical addressing
1. Click the Start button in order to begin the addressing procedure.
Addresses
If you have selected Complete new installation, all previous addresses will be deleted. Otherwise
you can add further devices to the existing addressing scheme. If you have not selected Delete all
group assignments, the assignment of addresses to groups is retained. Bear this in mind when re-
assign in the addresses!
2. The following instruction now appears in the status line:
Wait for a device to be selected. Remove the lamp!
3. After the lamp has been removed, the instruction that appears in the status line is as follows:
The device was addressed. Add the lamp again!
After reinserting the lamp, it flashes three times in order to indicate that the address assignment has
been successful.
The newly addressed device is now shown in the list of short addresses.
4. Repeat Point 2 and Point 3 for every DALI device that is to be re-addressed.
5. When you have assigned all the addresses, complete the addressing procedure by clicking the Cancel
button.
The newly addressed devices will be shown in the list of short addresses:
Fig. 24: KS2000 - addressing of the DALI device - displaying the physical addressing
Random addressing
With this method, addresses are assigned randomly.
36
Version: 2.0.0
KL6811

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ks6811

Table of Contents